TROUBLE SHOOTING THE GAS CONTROL SYSTEM
SIT 820 NOVA MILLIVOLT VALVE
START CHECK
GLASS DOOR TO BE REMOVED BEFORE SERVICE WORK
GAS SUPPLY ON
• SHUTOFF VALVE OPEN
• CONFIRM GAS HOOK-UP
LIGHT PILOT WITH
PIEZO IGNITION
ELECTRODE GAP MIN. 1/8"
• ELECTRODE CRACKED
• ELECTRODE CABLE ATTACHED
• PIEZO IGNITOR GENERATES
SPARK
• ELECTRODE CABLE NOT
GROUNDED
PILOT STAYS ON
FLAME ENGULFING
THERMOCOUPLE BY 3/8"
THERMOCOUPLE ATTACHED
TO VALVE
MNIMUM MILLIVOLT:
OPEN CIRCUIT 18MV
CLOSED CIRCUIT 5MV
VENT SAFETY SWITCH TIGHT
AND NO SHORTS
(FOR UNITS EQUIPPED WITH
VENT SAFETY SWITCH)
MAIN BURNER ON
REMOTE SYSTEM ON
REMOTE SYSTEM WIRE
SHORTING OUT
MINIMUM MILLIVOLT:
OPEN CIRCUIT 300MV
CLOSED CIRCUIT 165MV
FLAME ENGULFING
THERMOPILE/THERMOCOUPLE
VALVE IS IN ON POSITION
NO
NO
NO
YES
YES
NO