CONTROL CONFIGURATION
KEYBOARD
ENTRY
DISPLAY
DESCRIPTION
VALUES IN [ ] INDICATE FACTORY DEFAULTS
LOG ON
Enter password followed by
ENTER
LOGGEDON Logged on okay
FACT CFG Factory configuration
TYPE X Unit type (0 = CV, 1 = VAV) [Default is 1]
ENTER
x
TYPE X Verify unit type and change if necessary. If CV unit, see CV
control configuration.
DTRS Data Reset
Enable Data Reset
ENTER
FACT CFG Factory Configuration
LLAG X
Use to access lead/lag option — disable with
HGBP (Item D, page CL-1)
ENTER
DISABLE Disable lead/lag (0 = DIS, 1 = ENB) [1]
BLD PRES Configure building pressure control (modulating power
exhaust)
BPS .05
Use for building pressure set point (range 0 to .5) [.05]
ENTER
x
BPS X Set building pressure set point per job requirements
LOGGEDON Access log on/off function
LOG OFF Use to access log off
ENTER
LOGD OFF
Logged off okay
INPUTS Run quick test to verify operation of unit functions
(see Controls and Troubleshooting Guide)
through
SETPOINT Set system set points per job requirements
OHSP X Set occupied heat set point (Range 55-80 F) [68] CV only
OCSP X
Set occupied cool set point (Range 55-80 F) [78] CV only
UHSP X
Set unoccupied heat set point (Range 40-80 F) [55]
UCSP X
Set unoccupied cool set point (Range 75-95 F) [90]
SPSP X
Set supply duct pressure set point (Range 0-5.0 in. wg) [1.5]
SASP X Set supply air set point temperature (Range 45-70 F) [55]
TIME Current time/date
dow.hh.mm Set day of week and time
mm.dd.yy Set month, day, and year
DAYLIGHT Set daylight savings time begin/end dates. Required if job
conditions requireadjustment ofclock fordaylightsavings time
(see Controls and Troubleshooting Guide)
HOLIDAY Set holidaydates. Requiredif jobconditions requirea different
scheduleon holidaysthanother days(seeControls andTrouble-
shooting Guide)
PERIOD X Set occupied/unoccupied schedules. Required if job condi-
tions require unit to enter unoccupied cycle at programmed
times of day or days of week (see Controls and Troubleshoot-
ing Guide)
through
NOTE: Data in brackets [ ] is default value.
CL-3