Carrier 33CS400-01 Thermostat User Manual


 
Select the security level:
0=No security in effect
1=Setpoint range limited
2=1+ locked in current
mode.
3=2 + prohibits setpoint
changes
Adjust the minimum
allowable cool setpoint
when security is in effect.
(35 - 99 )
Press
MODE
Press
MODE
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
HUMIDITY
Press
When a security level has been programmed, the thermostat will allow
limited adjustment to the setpoints (steps # 6 and 7). In security
levels 2 and 3, the thermostat is forced into the Program On mode.
To disable the security feature, set the value in step #5 to 0; this will
cause steps # 6 and 7 not to appear.
Page 7.4
Programming a Security LevelProgramming a Security Level
0
Setup
5
HEAT
80
Setup
6
COOL
65
Setup
7
Adjust the maximum
allowable heat setpoint
when security is in effect.
(35 - 99 )
Step #6 appears only
if step #5 is not 0.
Step #7 appears only
if step #5 is not 0.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
7
HUMIDITY
MODE
MODE
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
Press the MODE button repeatedly
until this setup screen appears.
HI
LO