RADIUS 20 [508]
CONTROL BOX
HINGED ACCESS
88.50 [2247.9]
1.50
38.1[]
1.50
38.1[]
SEE NOTE #3
TYP.
1.00 25.4[]
SEE NOTE #3
TYP.
1.00 25.4[]
4.63
117.6[]
27.98
710.7[]
7/8 [22.4]
FIELD POWER ENTRY
SEE NOTE #2
44.00
1117.6[]
11.20
284.5[]
31.74
806.2[]
Y
X
H
SEE NOTE #5
42 [1067] MIN.
48 [1219] MIN.
42 [1067] MIN.
48 [1219] MIN.
92.50 [2349.5]
UNIT
CENTER OF GRAVITY UNIT HEIGHT VICTAULIC CONNECTIONS
X Y H (STANDARD) H (VALUE SOUND) WATER IN/OUT
30RA035
36.45 [926] 46.08 [1170] 66.5 [1689] 61.0 [1549] 2-1/2"
30RA040
36.24 [921] 44.03 [1118] 66.5 [1689] 61.0 [1549] 2-1/2"
30RA045
36.24 [921] 46.15 [1172] 78.5 [1994] 73.0 [1854] 2-1/2"
30RA050
36.00 [914] 44.00 [1118] 78.5 [1994] 73.0 [1854] 2-1/2"
30RA055
36.48 [927] 44.60 [1133] 78.5 [1994] 73.0 [1854] 2-1/2"
30RA060
36.50 [927] 44.56 [1132] 78.5 [1994] 73.0 [1854] 2-1/2"
REAR VIEW
CONTROL BOX
HINGED ACCESS
CIRCUIT A
COMPRESSOR
ACCESS
COIL
AREA
AIR FLOW
AIR FLOW
FRONT VIEW
CIRCUIT B
COMPRESSOR
ACCESS
TOP VIEW
RIGHT VIEW
COIL
AREA
SERVICE
CLEARANCE
BORDER
(NOT TO SCALE)
CG
NOTES:
1. DO NOT CAP OR OTHERWISE OBSTRUCT THE
LIQUID LINE TEMPERATURE RELIEF.
2. 7/8 [22.4] PILOT HOLE PROVIDED FOR LOCATING FIELD POWER WIRING.
ACTUAL HOLE REQUIRED DEPENDS ON FIELD WIRE SIZING.
3. 0.437 [11.10] HOLE USED FOR MOUNTING UNIT.
4. UNIT MUST HAVE CLEARANCES AS FOLLOWS:
TOP - DO NOT RESTRICT.
COIL SIDE - 42 [1067] FROM SOLID SURFACE.
PANEL SIDE - 48 [1219] PER NEC.
5. SEE TABLE COLUMN H; DIMENSION FOR STANDARD FAN OR VALUE
SOUND FAN OPTION.
6. CARRIER DOES NOT RECOMMEND INSTALLATION IN A PIT.
7. UNIT CAN BE HANDLED USING THE FORK TRUCK LIFT POCKETS
(MINIMUM OF 60" FORK LENGTH).
8. WATER CONNECTIONS RECESSED 4-1/2 INCHES INSIDE UNIT.
DIMENSIONS IN [ ] ARE IN MILLIMETERS
VALUE SOUND FAN OPTION
(PICTORIALLY ONLY)
AIR FLOW
FIELD
CONTROL
WIRING
CONNECTIONS
FORK
TRUCK
POCKETS
NOTE: 3 OR 4 FANS
PANEL SIDE
SEE NOTE #4
COIL SIDE
SEE NOTE #4
PANEL SIDE
SEE NOTE #4
COIL SIDE
SEE NOTE #4
WATER-IN
WATER-OUT
9. DIMENSIONS ARE IN INCHES.
Fig. 7 — Dimensions — 30RAP035-060 Units
a30-4950