Carrier 30RAP010-060 Air Conditioner User Manual


 
22
Table 11 — 30RAP Electrical Data — Hydronic Package with Standard Low-Sound AeroAcoustic™ Fan
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. All units/modules have single point primary power connection. (Each unit/module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 1 hp
PUMP OPTIONS "1" OR "8"
PUMP SIZE 1.5 hp
PUMP OPTIONS "2" OR "9"
PUMP SIZE 2 hp
PUMP OPTIONS "3" OR "B"
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
010
208/230-60 69.4 110 254.3 90 70.6 110 255.4 90 71.7 110 256.6 90
380-60 35.5 50 253.0 45 36.2 50 151.6 45 60.5 60 152.2 45
460-60 27.8 45 252.6 35 28.4 45 130.1 35 28.9 45 130.6 35
575-60 22.1 35 252.3 30 22.6 35 104.2 30 22.9 35 104.5 30
015
208/230-60 79.0 125 349.3 100 80.2 125 350.4 100 81.4 125 351.6 100
380-60 48.4 80348.0 60 49.1 80 202.6 60 83.7 80 203.2 60
460-60 38.2 60 347.6 45 38.7 60 184.1 50 39.2 60 184.6 50
575-60 33.3 50 347.3 40 33.8 50 136.2 40 34.2 50 136.5 45
018
208/230-60 90.4 110 273.7 100 91.6 110 274.8 100 92.8 125 276.0 110
380-60 53.0 70 272.4 60 53.8 70 169.7 60 73.6 70 170.3 60
460-60 45.0 60 272.0 50 45.6 60 13
8.7 50 46.1 60 139.2 60
575-60 36.2 45 271.7 40 36.7 50 100.0 45 37.0 50 100.3 45
020
208/230-60 95.8 125 290.1 110 97.0 125 291.2 110 98.2 125 292.4 110
380-60 63.1 80288.8 70 63.9 80 179.2 70 88.2 80179.880
460-60 47.7 60 288.4 60 48.3 60 150.9 60 48.8 60 151.4 60
575-60 38.3 50 288.1 45 38.8 50 100.9 45 39.2 50 101.3 45
025
208/230-60 130.7 175 366.6 150 131.9 175 367.7 150 133.0 175 368.9 150
380-60 70.3 90 365.3 80 71.0 90 176.4 8098.5 90 177.0 8 0
460-60 59.4 80 364.9 70 60.0 80181.1 70 60.5 80181.6 70
575-60 50.9 70 364.6 60 51.4 70 135.5 60 51.7 70 135.8 60
030
208/230-60 140.8 175 411.1 175 142.0 175 412.2 175 143.2 175 413.4 175
380-60 86.3 110 409.8 100 87.0 110 240.5 100 121.6 110 241.1 100
460-60 68.0 90 409.4 8068.5 90 213.9 8069.0 90 214.4
80
575-60 59.4 80 409.1 70 59.9 80 162.3 70 60.3 80 162.6 70
035
208/230-60 168.6 200 344.9 200 169.8 200 346.0 200 171.0 200 347.2 200
380-60 105.5 125 343.6 125 106.2 125 209.9 125 130.5 125 210.5 125
460-60 84.0 100 343.2 90 84.6 100 178.5 90 85.1 100 179.0 90
575-60 67.5 80342.98067.9 80 122.88068.3 80123.280
040
208/230-60 198.0 225 380.3 225 199.2 225 381.4 225 200.4 225 382.6 225
380-60 114.4 125 379.0 125 115.2 125 218.8 125 139.5 125 219.4 125
460-60 87.8 100 378.6 100 88.4 100 182.3 100 88.9 100 182.8 100
575-60 70.1 80378.3 8070.6 80 145.5 8071.0 80145.980
045
208/230-60 232.9 250 454.0 250 234.1 250 455.1 250 235.2 250 456.3 250
380-60 121.6 125 452.7 125 122.3 125 219.2 125 149.8 125 219.8 125
460-60 99.5 110 452.3 110 100.1 110 217.0 110 100.6 110 217.5 110
575-60 82.7 100 452.0 90 83.2 100 165.3 90 83.5 100 165.6 90
050
208/230-60 239.3 250 457.2 250 240.5 250 458.3 250 241.6 250 459.5 250
380-60 128.0 150 455.9 150 128.7 150 222.4 150 156.2 150 223.0 150
460-60 108.5 125 455.5 125 109.1 125 221.5 125 109.6 125 222.0 125
575-60 93.1 110 455.2 100 93.6 110 170.5 100 93.9 110 170.8 100
055
208/230-60 255.4 300 506.2 300 256.6 300 507.3 300 257.8 300 508.5 300
380-60 147.9 175 504.9 175 148.6 175 293.6 175 183.2 175 294.2 175
460-60 120.0 125 504.5 125 120.5 125 258.1 125 121.0 125 258.6 125
575-60 104.0 125 504.2 110 104.5 125 201.1 125 104.9 125 201.4 125
060
208/230-60 264.4 300 510.7 300 265.6 300 511.8 300 266.8 300 513.0 300
380-60 162.1 175 509.4 175 162.8 175 300.7 175 197.4 175 301.3 175
460-60 127.6 150 509.0 150 128.1 150 261.9 150 128.6 150 262.4 150
575-60 111.6 125 508.7 125 112.1 125 204.9 125 112.5 125 205.2 125
ICF Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection