Table 11 — 30RAP Electrical Data — Hydronic Package with Standard Low-Sound
AeroAcoustic™ Fan (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. All units/modules have single point primary power connection. (Each unit/module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 3 hp
PUMP OPTIONS "4" OR "C"
PUMP SIZE 5 hp
PUMP OPTIONS "5" OR "6" OR "D" OR "F"
PUMP SIZE 7.5 hp
PUMP OPTIONS "7" OR "G"
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
010
208/230-60 74.7 110 259.6 90 79.5 125 264.4 100 86.1 125 271.0 100
380-60 61.9 60 153.6 45 64.7 60 156.4 50 68.6 60 160.2 60
460-60 30.1 45 131.8 35 32.4 50 134.1 40 35.5 50 137.3 45
575-60 23.9 35 105.5 30 25.8 40 107.4 30 28.3 40 109.9 35
015
208/230-60 84.4 125 354.6 100 89.2 125 359.4 110 95.8 150 366.0 110
380-60 85.1 80 204.6 60 87.9 80 207.4 70 91.7 90 211.2 70
460-60 40.4 60 185.8 50 42.7 60 188.1 50 45.9 70 191.3 60
575-60 35.1 50 137.5 45 37.0 60 139.4 45 39.5 60 141.9 50
018
208/230-60 95.8 125 279.0 110 100.6 125 283.8 110 107.2 125 290.4 125
380-60 75.0 70 171.7 70 77.8 70 174.5 70 81.6 80178.4 70
460-60 47.3 60 140.4 60 49.6 60 142.7 60 52.7 60 145.9 60
575-60 38.0 50 101.3 45 39.9 50 103.2 45 42.3 50 105.6 50
020
208/230-60 101.2 125 295.4 125 106.0 125 300.2 125 112.6 125 306.8 125
380-60 89.6 80181.2 8092.4 90184.0 80 96.2 90 187.9 80
460-60 50.0 60 152.6 60 52.3 70 154.9 60 55.4 70 158.1 60
575-60 40.1 50 102.2 45 42.0 50 104.1 50 44.5 50 106.6 50
025
208/230-60 136.0 175 371.9 150 140.8 175 376.7 175 147.4 175 383.3 175
380-60 99.9 90 178.4 80 102.7 100 181.2 90 106.6 100 185.0 90
460-60 61.7 80182.8 70 64.0 80185.1 70 67.1 90 188.3 80
575-60 52.7 70 136.8 60 54.6 70 138.7 60 57.1 70 141.2 70
030
208/230-60 146.2 200 416.4 175 151.0 200 421.2 175 157.6 200 427.8 175
380-60 123.0 110 242.5 100 125.8 125 245.3 110 129.6 125 249.1 110
460-60 70.2 90 215.6 8072.5 90217.980 75.7 100 221.1 90
575-60 61.2 80 163.6 70 63.1 80 165.5 70 65.6 80168.0 80
035
208/230-60 174.0 200 350.2 200 178.8 200 355.0 200 185.4 200 361.6 200
380-60 131.9 125 211.9 125 134.7 125 214.7 125 138.6 125 218.5 125
460-60 86.3 100 180.2 100 88.6 100 182.5 100 91.7 100 185.7 100
575-60 69.2 80 124.1 8071.1 80126.080 73.6 80128.5 80
040
208/230-60 203.4 250 385.6 225 208.2 250 390.4 225 214.8 250 397.0 250
380-60 140.9 125 220.8 125 143.7 125 223.6 125 147.5 125 227.5 125
460-60 90.1 100 184.0 100 92.4 110 186.3 100 95.5 110 189.5 110
575-60 71.9 80 146.88073.880148.7 80 76.3 90 151.2 80
045
208/230-60 238.2 250 459.3 250 243.0 250 464.1 250 249.6 300 470.7 300
380-60 151.2 150 221.2 150 154.0 150 224.0 150 157.9 150 227.8 150
460-60 101.8 110 218.7 110 104.1 125 221.0 110 107.2 125 224.2 125
575-60 84.5 100 166.6 90 86.4 100 168.5 100 88.9 100 171.0 100
050
208/230-60 244.6 250 462.5 250 249.4 300 467.3 300 256.0 300 473.9 300
380-60 157.6 150 224.4 150 160.4 150 227.2 150 164.3 150 231.0 150
460-60 110.8 125 223.2 125 113.1 125 225.5 125 116.2 125 228.7 125
575-60 94.9 110 171.8 100 96.8 110 173.7 110 99.3 110 176.2 110
055
208/230-60 260.8 300 511.5 300 265.6 300 516.3 300 272.2 300 522.9 300
380-60 184.6 175 295.6 175 187.4 175 298.4 175 191.2 175 302.2 175
460-60 122.2 125 259.8 125 124.5 150 262.1 150 127.7 150 265.3 150
575-60 105.8 125 202.4 125 107.7 125 204.3 125 110.2 125 206.8 125
060
208/230-60 269.8 300 516.0 300 274.6 300 520.8 300 281.2 300 527.4 300
380-60 198.8 175 302.7 175 201.6 200 305.5 200 205.4 200 309.3 200
460-60 129.8 150 263.6 150 132.1 150 265.9 150 135.3 150 269.1 150
575-60 113.4 125 206.2 125 115.3 125 208.1 125 117.8 125 210.6 125
ICF Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection