Table 15 — Pump Electrical Data
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed minimum
and maximum limits. Maximum allowable phase imbalance is: volt-
age, 2%; amps 10%.
2. All units/modules have single point primary power connection.
(Each unit/module requires its own power supply.) Main power must
be supplied from a field-supplied disconnect.
3. The unit control circuit power transformer (24 v, single-phase for all
voltages) is factory supplied.
4. Cooler heaters are wired into the main power circuit so they are
always operable as long as the disconnect is on, even if any safety
device is open, and the unit ON/OFF switch is in the OFF position.
Table 16 — Accessory Tank Electrical Data
LEGEND
PUMP OPTION PUMP SIZE PUMP RPM
UNIT VOLTAGE
V-Hz (3 Ph)
FLA
(each)
1, 8 1.0 HP
3500 208/230-60 3.3
3500 380-60 2.0
3500 460-60 1.6
3500 575-60 1.3
2, 9 1.5 HP
3500 208/230-60 4.4
3500 380-60 2.7
3500 460-60 2.2
3500 575-60 1.8
3, B 2.0 HP
3500 208/230-60 5.6
3500 380-60 3.3
3500 460-60 2.7
3500 575-60 2.1
4, C 3.0 HP
3500 208/230-60 8.6
3500 380-60 4.7
3500 460-60 3.9
3500 575-60 3.1
5, 6, D, F 5.0 HP
3500 208/230-60 13.4
3500 380-60 7.5
3500 460-60 6.2
3500 575-60 5.0
7, G 7.5 HP
3500 208/230-60 20.0
3500 380-60 11.3
3500 460-60 9.4
3500 575-60 7.5
FLA Full Load Amps
UNIT VOLTAGE
(V-Hz)
ACCESSORY PART NO.
30RA-900---
FLA
208/230-60
050 11.3
051 11.3
052 22.6
460-60
050 5.7
051 5.7
052 11.3
575-60
050 4.5
051 4.5
052 9.1
380-60
050 6.8
051 6.8
052 13.7
FLA Full Load Amps