Carrier 30RAP010-060 Air Conditioner User Manual


 
25
Table 12 — 30RAP Electrical Data — Hydronic Package with Optional Value Sound Fans (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. All units/modules have single point primary power connection. (Each unit/module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 3 hp
PUMP OPTIONS "4" OR "C"
PUMP SIZE 5 hp
PUMP OPTIONS "5" OR "6" OR "D" OR "F"
PUMP SIZE 7.5 hp
PUMP OPTIONS "7" OR "G"
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
010
208/230-60 75.3 110 260.2 90 80.1 125 265.0 100 86.7 125 271.6 100
380-60 61.9 60 153.6 45 64.7 60 156.4 50 68.6 60 160.2 60
460-60 30.5 45 132.2 40 32.8 50 134.5 40 35.9 50 137.7 45
575-60 24.1 35 105.7 30 26.0 40 107.6 30 28.5 40 110.1 35
015
208/230-60 85.0 125 355.2 100 89.8 125 360.0 110 96.4 150 366.6 125
380-60 85.1 80204.66087.9 80 207.4 70 91.7 90 211.2 70
460-60 40.8 60 186.2 50 43.1 70 188.5 50 46.3 70 191.7 60
575-60 35.3 50 137.7 45 37.2 60 139.6 45 39.7 60 142.1 50
018
208/230-60 97.0 125 280.2 110 101.8 125 285.0 125 108.4 125 291.6 125
380-60 75.0 70 171.7 70 77.8 70 174.5 70 81.6 80178.4 70
460-60 48.1 60 141.2 60 50.4 60 143.5 60 53.5 70 146.7 60
575-60 38.4 50 101.7 45 40.3 50 103.6 45 42.7 50 106.0 50
020
208/230-60 102.4 125 296.6 125 107.2 125 301.4 125 113.8 125 308.0 125
380-60 89.6 80181.2 8092.4 90184.0 8096.2 90187.9 80
460-60 50.8 60 153.4 60 53.1 70 155.7 60 56.2 70 158.9 70
575-60 40.5 50 102.6 45 42.4 50 104.5 50 44.9 50 107.0 50
025
208/230-60 137.2 175 373.1 175 142.0 175 377.9 175 148.6 175 384.5 175
380-60 99.9 90 178.4 80 102.7 100 181.2 90 106.6 100 185.0 90
460-60 62.5 80183.6 70 64.880185.9 8067.9 90189.1 80
575-60 53.1 70 137.2 60 55.0 70 139.1 60 57.5 70 141.6 70
030
208/230-60 147.4 200 417.6 175 152.2 200 422.4 175 158.8 200 429.0 175
380-60 123.0 110 242.5 100 125.8 125 245.3 110 129.6 125 249.1 110
460-60 71.0 90 216.4 80 73.3 100 218.7 90 76.5 100 221.9 90
575-60 61.6 80 164.0 70 63.5 80 165.9 70 66.0 80168.4 80
035
208/230-60 175.8 200 350.2 200 180.6 200 355.0 200 187.2 200 361.6 200
380-60 131.9 125 211.9 125 134.7 125 214.7 125 138.6 125 218.5 125
460-60 87.5 100 180.2 100 89.8 100 182.5 100 92.9 110 185.7 100
575-60 69.880124.18071.7 80 126.0 8074.2 80128.5 80
040
208/230-60 205.2 250 385.6 225 210.0 250 390.4 225 216.6 250 397.0 250
380-60 140.9 125 220.8 125 143.7 125 223.6 125 147.5 125 227.5 125
460-60 91.3 100 184.0 100 93.6 110 186.3 100 96.7 110 189.5 110
575-60 72.5 80146.88074.4 80148.7 80 76.9 90 151.2 90
045
208/230-60 240.0 250 459.3 250 244.8 250 464.1 250 251.4 300 470.7 300
380-60 151.2 150 221.2 150 154.0 150 224.0 150 157.9 150 227.8 150
460-60 103.0 125 218.7 110 105.3 125 221.0 125 108.4 125 224.2 125
575-60 85.1 100 166.6 100 87.0 100 168.5 100 89.5 100 171.0 100
050
208/230-60 246.4 250 462.5 250 251.2 300 467.3 300 257.8 300 473.9 300
380-60 157.6 150 224.4 150 160.4 150 227.2 150 164.3 150 231.0 150
460-60 112.0 125 223.2 125 114.3 125 225.5 125 117.4 125 228.7 125
575-60 95.5 110 171.8 110 97.4 110 173.7 110 99.9 110 176.2 110
055
208/230-60 263.2 300 511.5 300 268.0 300 516.3 300 274.6 300 522.9 300
380-60 184.6 175 295.6 175 187.4 175 298.4 175 191.2 175 302.2 175
460-60 123.8 150 259.8 150 126.1 150 262.1 150 129.3 150 265.3 150
575-60 106.6 125 202.4 125 108.5 125 204.3 125 111.0 125 206.8 125
060
208/230-60 272.2 300 516.0 300 277.0 300 520.8 300 283.6 300 527.4 300
380-60 198.8 175 302.7 175 201.6 200 305.5 200 205.4 200 309.3 200
460-60 131.4 150 263.6 150 133.7 150 265.9 150 136.9 150 269.1 150
575-60 114.2 125 206.2 125 116.1 125 208.1 125 118.6 125 210.6 125
ICF Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection