8
RADIUS 20 [508]
CONTROL BOX
HINGED ACCESS
48 [1219] MIN.
36 [914] MIN.
36 [914] MIN.
42 [1067] MIN.
40.50 [1028.7]
FIELD POWER ENTRY
SEE NOTE #2
7/8 22.4[]
SEE NOTE #3
TYP.
1.00 25.4[]
SEE NOTE #3
TYP.
1.00 25.4[]
1.50 38.1[ ] 1.50 38.1[]
H
SEE NOTE #5
15.31
388.9[]
21.06 534.9[]
88.50 [2247.9]
P
X
Y
4.21
106.9[]
UNIT
CENTER OF GRAVITY UNIT HEIGHT POWER ENTRY VICTAULIC CONNECTIONS
XY
H (STANDARD) H (VALUE SOUND)
P WATER IN/OUT
30RA018
18.37 [467] 38.77 [985] 66.5 [1689] 61.0 [1549] 24.9 [631] 2"
30RA020
18.38 [467] 38.79 [985] 66.5 [1689] 61.0 [1549] 24.9 [631] 2"
30RA025
18.58 [472] 38.93 [989] 78.5 [1994] 73.0 [1854] 36.9 [936] 2"
30RA030
18.59 [472] 38.98 [990] 78.5 [1994] 73.0 [1854] 36.9 [936] 2"
CONTROL BOX
HINGED ACCESS
AIR FLOW
AIR FLOW
FRONT VIEW
COMPRESSOR
ACCESS
TOP VIEW
RIGHT VIEW
SERVICE
CLEARANCE
BORDER
(NOT TO SCALE)
SERVICE
ACCESS
CG
COIL
AREA
PANEL SIDE
SEE NOTE #4
COIL SIDE
SEE NOTE #4
NOTES:
1. DO NOT CAP OR OTHERWISE OBSTRUCT THE
LIQUID LINE TEMPERATURE RELIEF.
2. 7/8 [22.4] PILOT HOLE PROVIDED FOR LOCATING FIELD POWER WIRING.
ACTUAL HOLE REQUIRED DEPENDS ON FIELD WIRE SIZING.
3. 0.437 [11.10] HOLE USED FOR MOUNTING UNIT.
4. UNIT MUST HAVE CLEARANCES AS FOLLOWS:
TOP - DO NOT RESTRICT.
COIL SIDE - 42 [1067] FROM SOLID SURFACE.
PANEL SIDE - 48 [1219] PER NEC.
5. SEE TABLE COLUMN H; DIMENSION FOR STANDARD FAN OR VALUE
SOUND FAN OPTION.
6. CARRIER DOES NOT RECOMMEND INSTALLATION IN A PIT.
7. UNIT CAN BE HANDLED USING THE FORK TRUCK LIFT POCKETS.
8. WATER CONNECTIONS RECESSED 2-3/8 INCHES INSIDE UNIT.
DIMENSIONS IN [ ] ARE IN MILLIMETERS
VALUE SOUND FAN OPTION
(PICTORIALLY ONLY)
WATER-IN
WATER-OUT
FORK
TRUCK
POCKETS
9. DIMENSIONS ARE IN INCHES.
Fig. 6 — Dimensions — 30RAP018-030 Units
a30-4949