Carrier 30RAP010-060 Air Conditioner User Manual


 
28
Table 17 — Compressor Electrical Data
LEGEND
* All data is per individual compressor.
UNIT
30RAP
NUMBER OF
COMPRESSORS
PER CIRCUIT
UNIT VOLTAGE
V-Hz (3 Ph)
CIRCUIT*
CIRCUIT A CIRCUIT B
RLA LRA RLA LRA
010
1
208/230-60 48.1 245
380-60 23.7 145
460-60 18.6 125
575-60 14.7 100
015
1
208/230-60 55.8 340
380-60 34.0 196
460-60 26.9 179
575-60 23.7 132
018
2
208/230-60 33.4 225
380-60 19.2 140
460-60 16.7 114
575-60 13.4 80——
020 2
208/230-60 35.8 239
380-60 23.7 145
460-60 17.9 125
575-60 14.3 80——
025 2
208/230-60 51.3 300
380-60 26.9 139
460-60 23.1 150
575-60 19.9 109
030 2
208/230-60 55.8 340
380-60 34.0 196
460-60 26.9 179
575-60 23.7 132
035 2
208/230-60 35.8 239 33.4 225
380-60 23.7 145 19.2 140
460-60 17.9 125 16.7 114
575-60 14.3 8013.480
040 2
208/230-60 35.8 239 48.1 245
380-60 23.7 145 23.7 145
460-60 17.9 125 18.6 125
575-60 14.3 80 14.7 100
045 2
208/230-60 48.1 245 51.3 300
380-60 23.7 145 23.7 145
460-60 18.6 125 23.1 150
575-60 14.7 100 19.9 109
050 2
208/230-60 51.3 300 51.3 300
380-60 26.9 139 26.9 139
460-60 23.1 150 23.1 150
575-60 19.9 109 19.9 109
055 2
208/230-60 51.3 300 55.8 340
380-60 26.9 139 34.0 196
460-60 23.1 150 26.9 179
575-60 19.9 109 23.7 132
060 2
208/230-60 55.8 340 55.8 340
380-60 34.0 196 34.0 196
460-60 26.9 179 26.9 179
575-60 23.7 132 23.7 132
LRA Locked Rotor Amps
RLA Rated Load Amps