PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
549B072 (6 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/Bf
1800/0.06 2100/0.066 2400/0.071 3000/0.088
Indoor Entering Air Ewb (F)
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
75
TC
83.2 77.6 71.6 67.9 84.7 79.8 73.6 71.5 85.9 81.0 75.0 74.3 88.4 82.9 78.4 78.3
SHC
39.7 50.4 60.6 66.6 41.6 54.3 65.9 70.1 43.4 57.6 70.6 72.8 47.2 63.9 76.9 76.8
kW
4.90 4.78 4.69 4.63 4.94 4.84 4.71 4.69 4.97 4.86 4.74 4.73 5.04 4.91 4.81 4.81
85
TC
81.5 75.5 69.0 64.8 83.2 77.3 71.1 69.4 84.5 78.5 72.7 72.2 86.2 80.8 76.5 76.5
SHC
39.2 49.8 59.6 63.6 41.4 53.5 65.0 68.0 43.3 56.9 69.7 70.8 47.1 64.1 75.0 75.0
kW
5.45 5.34 5.23 5.16 5.49 5.36 5.27 5.23 5.52 5.38 5.29 5.27 5.57 5.45 5.36 5.36
95
TC
78.8 72.5 64.1 61.8 80.9 74.5 67.0 66.1 82.0
76.0 69.9 69.9 83.7 78.1 74.2 74.1
SHC
38.4 48.6 57.4 60.6 40.8 52.6 63.2 64.8 42.8 56.4 68.3 68.5 46.8 63.7 72.7 72.7
kW
6.03 5.91 5.79 5.73 6.09 5.96 5.84 5.82 6.11
6.00 5.89 5.89 6.16 6.05 5.96 5.96
105
TC
76.2 69.5 58.6 57.8 77.9 71.3 63.4 63.1 79.3 72.7 67.2 67.2 81.1 74.5 71.3 71.2
SHC
37.6 47.4 55.0 56.6 39.9 51.4 61.4 61.9 42.2 55.3 65.9 65.9 46.5 62.5 69.9 69.9
kW
6.69 6.56 6.40 6.38 6.73 6.61 6.45 6.44 6.77 6.64 6.51 6.51 6.82 6.67 6.57 6.57
115
TC
72.5 65.1 54.8 54.7 74.3 67.8 58.6 58.6 75.6 69.1 63.2 63.2 77.3 70.9 68.4 68.4
SHC
36.3 45.8 53.2 53.6 38.7 50.2 57.4 57.5 41.1 54.0 62.0 62.0 45.5 61.3 67.1 67.1
kW
7.37 7.24 7.08 7.07 7.43 7.30 7.16 7.16 7.48 7.34 7.21 7.21 7.52 7.38 7.32 7.32
549B090 (7
1
/
2
Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/Bf
2250/0.12 3000/0.15 3750/0.18
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
97.6 92.5 84.3 100.8 95.6 89.9 101.6 97.8 91.7
SHC
47.7 61.0 72.7 51.5 67.3 83.8 55.0 74.4 89.7
kW
5.80 5.76 5.73 5.86 5.78 5.78 5.86 5.82 5.73
85
TC
97.2 89.9 79.8 100.0 94.1 86.7 102.4 96.0 89.9
SHC
48.1 60.2 70.5 51.7 68.1 82.4 55.8 74.1 89.3
kW
6.61 6.50 6.43 6.65 6.56 6.62 6.69 6.58 6.50
95
TC
94.4 86.9 75.0 98.2
91.3 81.8 99.6 93.7 87.3
SHC
47.3 59.2 68.1 51.7 67.5 79.8 55.0 74.8 87.3
kW
7.43 7.37 7.19 7.50 7.41 7.30 7.50 7.43 7.35
105
TC
91.7 82.2 70.7 94.8 87.3 76.6 97.0 90.1 83.4
SHC
46.3 57.4 65.9 50.9 66.3 76.4 54.8 74.1 83.4
kW
8.37 8.22 8.04 8.39 8.33 8.15 8.44 8.35 8.26
115
TC
87.7 77.4 66.9 91.7 81.6 72.5 93.9 85.3 78.8
SHC
44.9 55.4 64.0 50.3 64.2 72.5 55.0 72.5 78.6
kW
9.33 9.16 8.98 9.44 9.27 9.11 9.48 9.33 9.22
125
TC
83.6 73.3 66.7 87.1 76.0 69.1 89.5 79.0 74.4
SHC
43.6 53.9 63.8 48.7 62.0 69.1 53.7 70.1 74.4
kW
10.38 10.16 9.94 10.49 10.27 10.14 10.53 10.36 10.25
549B120 (10 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/Bf
3000/0.03 4000/0.04 5000/0.06
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
136.0 124.0 111.4 141.2 129.0 116.6 145.6 132.0 121.2
SHC
64.6 80.8 96.0 71.2 92.4 111.8 78.6 103.2 121.0
kW
7.51 7.35 7.20 7.61 7.45 7.29 7.72 7.53 7.39
85
TC
132.6 119.6 106.6 137.6 124.4 112.0 140.4 127.4 118.0
SHC
63.6 79.2 94.0 70.6 91.4 110.0 77.0 102.6 118.0
kW
8.40 8.23 8.09 8.50 8.33 8.17 8.58 8.40 8.27
95
TC
127.8 114.6 99.4 133.2
119.4 107.2 136.2 121.8 114.2
SHC
62.2 77.6 90.8 69.6 89.8 107.0 76.8 101.2 113.8
kW
9.36 9.18 9.01 9.48
9.30 9.15 9.56 9.36 9.24
105
TC
122.4 108.8 92.0 127.4 113.6 101.4 130.4 116.0 109.6
SHC
60.4 75.4 87.4 68.0 88.0 101.4 75.4 99.4 109.4
kW
10.41 10.26 10.02 10.53 10.35 10.22 10.63 10.43 10.35
115
TC
116.8 101.8 86.6 121.2 106.6 94.8 123.6 109.2 104.6
SHC
58.6 72.8 84.6 66.0 85.4 94.8 73.4 97.0 104.6
kW
11.58 11.37 11.15 11.68 11.51 11.35 11.76 11.60 11.51
125
TC
110.6 95.8 84.6 114.6 98.4 88.8 117.0 100.8 96.4
SHC
56.4 70.6 83.4 64.4 82.4 88.8 71.4 93.8 96.4
kW
12.87 12.62 12.36 12.97 12.73 12.60 13.03 12.83 12.77
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not
extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator
coil
3. The SHC is based on 80 F edb temperature of air
entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from
SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
Bf
Bypass Factor
Edb
Entering Dry-Bulb
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity
(Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
total capacity
(Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR
DRY-BULB TEMP (F)
79 78 77 76 75
under
75
81 82 83 84 85
over
85
Correction Factor
.05
1.04 2.07 3.11 4.14 5.18 Use
formula
shown
below.
.10
.98 1.96 2.94 3.92 4.90
.20
.87 1.74 2.62 3.49 4.36
.30
.76 1.53 2.29 3.05 3.82
50TFQ004-012
549B036-120