Bryant 542J Heat Pump User Manual


 
55
PERFORMANCE DATA (cont)
INDOOR-FAN MOTOR PERFORMANCE 548F UNITS
LEGEND
BHP
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using your fan motors
up to the horsepower ratings shown in this table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
Single-phase/three-phase.
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
UNIT
548F
INDOOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY (%)
036
Standard
208/230
0.34 440
3.3
75
460 1.8
575 1.8
Alternate
208/230
1.00 1000
5.1
460 2.2
575 2.2
High Static
208/230
2.40 2120
6.1
460 2.7
575 2.7
048
Standard
208/230
0.75 850
3.1
75
460 1.9
575 1.9
Alternate
208/230
1.00 1000
5.1
460 2.2
575 2.2
High Static
208/230
2.40 2120
6.1
460 2.7
575 2.7
060
Standard
208/230
1.20 1340
6.2
74
460 3.4
575 3.4
Alternate
208/230
1.30/2.40 2120
9.2/6.1
460 2.7
575 2.7
High Static
208/230
2.90 2562
6.1
460 2.7
575 2.7
072
Standard
208/230
2.40 2120
6.1
84
460 2.7
575 2.7
High Static
208/230
2.90 2562
7.9
460 3.6
575 3.6
090
Standard,
Alternate
208/230
2.40 2120
6.1
80
460 2.7
575 2.7
High Static
208/230
3.70 3313
11.1
460 5.0
575 5.0
102
Standard
208/230
2.40 2120
6.1
80
460 2.7
575 2.7
High Static
208/230
3.70 3313
11.1
460 5.0
575 5.0
120
Standard
208/230
2.40 2120
6.1
80
460 2.7
575 2.7
Alternate
208/230
2.90 2615
7.9
460 3.6
575 3.6
High Static
208/230
5.25 4400
15.0
460 7.4
575 7.4
50TFQ004-012
548F036-120