PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving
indoor coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC..
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
INSTANTANEOUS AND INTEGRATED HEATING RATINGS
LEGEND NOTES:
1. indicates integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.
548F120 (10 TONS)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/BF
2800/0.11 3750/0.16 4100/0.18 4700/0.21
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
127.4 120.4 110.6 134.2 126.2 116.2 135.6 127.4 117.8 137.0 129.0 120.6
SHC
60.0 76.4 91.0 66.2 86.0 104.4 67.8 89.0 108.8 70.2 93.4 115.6
kW
8.30 8.18 7.88 8.54 8.34 8.04 8.60 8.36 8.10 8.64 8.38 8.20
85
TC
124.6 116.2 106.4 131.0 122.0 112.4 132.4 123.6 114.0 133.8 126.0 116.4
SHC
59.2 74.6 89.4 65.4 84.8 103.6 67.4 88.4 107.4 70.0 94.2 112.8
kW
9.24 9.04 8.74 9.50 9.24 8.98 9.54 9.28 9.02 9.60 9.36 9.08
95
TC
121.8 112.0 102.2 126.2 117.4 107.4 127.8 119.0 109.4 130.0 121.2 112.6
SHC
58.4 73.2 87.4 63.8 83.4 101.0 66.0 87.2 104.8 69.6 93.4 110.2
kW
10.34 10.04 9.66 10.46 10.18 9.90 10.52 10.26 9.96 10.62 10.36 10.08
105
TC
116.9 107.2 97.6 122.4 112.4 102.8 123.6 113.8 105.0 124.6 115.6 108.4
SHC
56.6 71.4 85.4 63.0 82.0 98.4 65.0 85.8 101.8 67.8 91.4 106.2
kW
11.38 11.08 10.66 11.64 11.28 10.90 11.68 11.32 11.00 11.68 11.38 11.16
115
TC
112.0 102.0 92.8 116.6 107.0 98.0 118.0 108.2 100.2 120.0 110.0 103.8
SHC
55.0 69.6 83.2 61.2 80.2 95.2 63.6 84.2 98.0 67.4 90.2 101.8
kW
12.58 12.18 11.74 12.78 11.42 12.00 12.84 12.48 12.12 12.96 12.56 12.30
125
TC
106.4 96.8 87.8 110.4 101.2 93.6 111.6 102.2 95.8 113.6 103.8 99.0
SHC
53.2 67.4 80.8 59.2 78.4 91.4 61.4 82.2 94.0 65.4 88.0 97.2
kW
13.84 13.36 12.90 13.96 13.62 13.22 14.02 13.68 13.34 14.14 13.76 13.54
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input
Ldb
Leaving Dry-Bulb
Lwb
Leaving Wet-Bulb
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79 78 77 76 75 under 75
81 82 83 84 85 over 85
Correction Factor
.05
1.04 2.07 3.11 4.14 5.18
Use formula
shown below.
.10
.98 1.96 2.94 3.92 4.90
.20
.87 1.74 2.62 3.49 4.36
.30
.76 1.53 2.29 3.05 3.82
548F036
Return
Air
(F db)
Cfm
(Standard
Air)
Air Temperature Entering Outdoor Coil (F)
0 10173040475060
55
900
Cap.
15.4
13.1 19.2 17.6 21.7 19.8 27.4 24.0 31.9 31.9 35.3 35.3 36.9 36.9 41.4 41.4
kW
2.25 2.44 2.57 2.86 3.10 3.29 3.38 3.64
1200
Cap.
15.9
13.5 19.4 17.8 22.5 20.5 28.3 24.8 32.9 32.9 35.8 35.8 37.0 37.0 40.1 40.1
kW
2.24 2.40 2.54 2.80 3.02 3.15 3.21 3.35
1500
Cap.
16.2
13.8 19.8 18.2 22.9 20.9 28.8 25.2 33.1 33.1 35.3 35.3 36.5 36.5 38.6 38.6
kW
2.23 2.38 2.52 2.76 2.94 3.03 3.08 3.17
70
900
Cap.
13.2
11.2 17.1 15.7 20.0 18.2 25.4 22.2 29.8 29.8 33.2 33.2 34.7 34.7 40.1 40.1
kW
2.29 2.50 2.67 2.98 3.24 3.45 3.55 3.91
1200
Cap.
13.7
11.6 17.7 16.3 20.3 18.5 26.3 23.1 30.8 30.8 34.4 34.4 36.0 36.0 40.9 40.9
kW
2.28 2.49 2.62 2.93 3.17 3.36 3.45 3.72
1500
Cap.
14.0
11.9 18.1 16.6 20.7 18.9 26.9 23.6 31.6 31.6 35.1 35.1 36.9 36.9 40.2 40.2
kW
2.27 2.47 2.60 2.89 3.12 3.30 3.38 3.54
80
900
Cap.
11.5
9.8 15.5 14.2 18.4 16.8 23.7 20.8 28.1 28.1 31.7 31.7 33.2 33.2 38.5 38.5
kW
2.30 2.54 2.71 3.04 3.32 3.55 3.65 4.03
1200
Cap.
12.0
10.2 16.2 14.8 19.2 17.5 24.7 21.6 29.3 29.3 33.0 33.0 34.5 34.5 40.2 40.2
kW
2.30 2.52 2.69 2.99 3.26 3.47 3.56 3.91
1500
Cap.
12.3
10.5 16.6 15.2 19.7 18.0 25.4 22.3 30.1 30.1 33.7 33.7 35.3 35.3 39.2 39.2
kW
2.29 2.51 2.68 2.97 3.22 3.41 3.50 3.70
Cap.
Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
db
dry bulb
kW
Total Power Input (includes compressor motor power input,
outdoor-fan motor input, and indoor-fan motor input)
50TFQ004-012
548F036-120