Bryant 542J Heat Pump User Manual


 
18
MODEL NUMBER NOMENCLATURE — 548F UNITS
(ODS Model Number)
ARI* CAPACITY RATINGS
548F036-060
548F072-120
LEGEND
*Air Conditioning and Refrigeration Institute.
Applies only to units with capacity of 60,000 Btuh or less.
**The IPLV applies only to 2-stage heat pump units.
††Not ASHRAE 90.1-99 compliant.
NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.
3. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air temperature and 95 F db
air entering outdoor unit.
IPLV Standard:
80 F db, 67 F wb indoor entering-air temperature and 80 F db out-
door entering-air temperature.
High-Temp Heating Standard:
70 F db indoor entering-air temperature and 47 F
db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard:
70 F db indoor entering-air temperature and 17 F
db, 15 F wb outdoor entering-air temperature.
UNIT
548F
NOMINAL
TONS
COOLING
HEATING
(High Temp)
SOUND
RATING
(decibels)
Capacity
(Btuh)
SEER†
Capacity
(Btuh)
HSPF
Belt
Drive
Direct
Drive
036
3 35,600 10.20 10.00 34,400 6.7 84
048
4 46,500 10.00 9.70 46,500 7.0 80
060
5 57,000 10.00 9.90 57,000 7.5 82
UNIT
548F
NOMINAL
TONS
COOLING
HEATING
(High)
HEATING
(Low)
IPLV**
SOUND
RATING
(decibels)
Capacity
(Btuh)
EER
Capacity
(Btuh)
COP
Capacity
(Btuh)
COP
072††
6 70,000 9.05 72,400 3.20 42,000 2.14 82
090††
7
1
/
2
86,000 9.00 78,000 3.00 39,000 1.80 9.3 86
102††
8
1
/
2
96,000 8.90 96,000 3.00 55,000 2.00 8.85 86
120††
10 112,000 9.00 105,000 3.10 59,000 2.00 9.0 84
COP
Coefficient of Performance
db
dry bulb
EER
Energy Efficiency Ratio
HSPF
Heating Seasonal Performance Factor
IPLV
Integrated Part-Load Values
SEER
Seasonal Energy Efficiency Ratio
wb
wet bulb
Voltage Designation
E 460-3-60
J 208/230-1-60
P 208/230-3-60
T 575-3-60
548F E X 090 000 AA
548F Single-Package
Heat Pump
Unit
X No Heat Installed.
(Field-installed electric heaters available.)
Factory-Installed Options*
Nominal Tons
036 3 090 7-1/2
048 4 102 8-1/2
060 5 120 10
072 6
Electric Heaters
000 No factory-installed electric heaters
LEGEND
*Refer to Trade Price Sheets or contact your local representative for specific
information regarding which options are available on which units.
Single-phase is only available on 036-060 size units.
NOTE:
The example model number 548FEX090000AA designates a 7
1
/
2
ton
460-3-60 volt electric heat pump unit with factory-installed economizer.
ODS
Order Distribution System
50TFQ004-012
548F036-120