Bosch Appliances 12/18 Boiler User Manual


 
CABINET MOUNTED LOW LEVEL
FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07)
14
PRE -
INSTALLATION
Minimum dimensions of flue terminal positions for oil fired appliances:
TERMINAL POSITION B(H)
A
1
Directly below an opening, air brick, opening windows, etc 600mm
B
1
Horizontally to an opening, air brick, opening window, etc 600mm
C Below a plastic/painted gutter, drainage pipe or eaves if 75mm
combustible material protected
D
2
Below a plastic/painted gutter, drainage pipe or eaves without 600mm
protection to combustible material
E From vertical sanitary pipework 300mm
F From an external or internal corner or from a surface or boundry 300mm
alongside the terminal
G Above ground or balcony level 300mm*
H
1
From a surface or boundary facing the terminal with 2500mm 1200mm
clearance to both sides of the terminal
H
2
From a surface or boundary facing the terminal with less than 2500mm
2500mm clearance to either side of the terminal
I
1
From a terminal facing the terminal with 2500mm clearance to 1200mm
clearance to both sides of the terminal
I
2
From a terminal facing the terminal with less than 2500mm 2500mm
clearance to either side of the terminal
K Horizontally from a terminal 750mm
B(H) Balanced Horizontal flue
1 An opening means an openable
element, such as an openable
window, or a permanent opening
such as a permanently open air vent.
Notwithstanding the dimensions
above, a terminal should be at least
300mm from combustible material,
e.g. a window frame.
2 A way of providing protection of
combustible material would be to fit
a heat shield at least 750mm wide.
Flue terminals must be positioned to avoid
combustion products entering into buildings.
The flue must be fitted and terminated in
accordance with the recommendations of
BS5410.
The flue must not cause an obstruction.
Discharge from the flue outlet must not be a
nuisance.
Flue gases have a tendency to plume and in
certain weather conditions a white plume of
condensation will be discharged from the flue
outlet which could be regarded as a
nuisance, for example, near security lighting.
There should be no restriction preventing the
clearance of combustion products from the
terminal.
The air inlet/outlet duct and the terminal of
the boiler must not be closer than 25mm to
any combustible material. Detailed
recommendations on protection of
combustible materials are given in BS 5410:1
A protective terminal guard must be fitted if
the terminal is 2m or less above a surface
where people have access.
Stainless steel terminal guard.
Part No: 7 716 190 050
The following additional guidelines (from part
L Exceptions Guidance Document) are
recommended when determining the flue
outlet position:
• Avoid discharging flue gases into car ports
or narrow passageways.
• *Minimum distance of the flue terminal from
above ground is 2100mm where directed to a
public footpath, private access route or a
frequently used area and 2500mm from a
car parking area.
boundary
F
I
H
B
A
G
E
C, D
F
F
J
K
boundary