Avalon Stoves 21 DV Fireplace Indoor Fireplace User Manual


 
Installation (for qualified installers only) 9
© Travis Industries 4040830 100-01143
Fireplace Placement Requirements
Minimum Framing Dimensions
The fireplace requires a 1/2" space between the fireplace and the framing members (or other
materials) along the sides and back of the fireplace. The stand-offs (and nailing brackets) may
contact the framing members but no material may be placed into the 1/2" space.
Route the electrical line to a position
to the right rear of the fireplace.
Thermostat or Remote
Control Wire (either side)
If using an elbow directly off the fireplace,
the vent will be centered 41-3/4" above
the base of the fireplace.
1/2" Clearance to the front, 0" to the sides, 1" below,
and 2" above the vent to combustibles.
The fireplace enclosure must be a minimum
48" above the base of the fireplace. NOTE:
Do not build into the area above the
fireplace (except for the required framing
members).
20-1/4"
36"
48" Min.
15-1/2"
Firestop
(required)
HINT: We recommend installing the
shaded framing after the fireplace is in
place.
WARNING: A cut-out for the gas line will be
required on the framing. See the dimensions
on page 6 and "Gas Line Connection" for
details.
HINT: we recommend reinforcing the
upper corners of the fireplace opening.
6"
5"
1"
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or
carpet)
This heater may be placed in a bedroom. Please be aware of the large amount of heat this
appliance produces when determining a location.
Clearances
When installed, walls in front of the fireplace must be a minimum 1" to the side of the
faceplate.
Due to the high temperature, the heater should be located out of traffic and away from furniture
and draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked