Avalon Stoves 21 DV Fireplace Indoor Fireplace User Manual


 
26 Installation (for qualified installers only)
© Travis Industries 4040830 100-01143
Facing Detail –Facing Over 1” Thick (Brick)
WARNING: Any facing that extends in front of the faceplate on the sides or top must be non-
combustible.
NOTE: A 3/8” gap is required above the face for face installation.
Top View
NOTE: Make sure to leave a 1/8" gap
around the sides of the face and 3/8"
above (for face installation).
Fireplace
Face
Drywall
Framing
Non-combustible facing material (brick, stone,
marble, tile) - required if the facing extends in
front of the face on the sides or top.
3/8"
The facing is brought up
to the wall trim.
The side facing should be spaced 1/8"
from the face (3/8 from the stand-offs).
Wall Trim
Side View
Fireplace
NOTE: Make sure to bring the facing up
to the wall trim.
In this example brick is used.
1/8"
3-d View
1/4" Nutdriver
Arched Face Thick Facing Template Part #
225-20040
The Arched Face Thick Facing Template is a
separate component that is required when
using an arched face with facing that extends
beyond the face (e.g.: brick, river rock). It
attaches to the top stand-off with the included
screws. The top edge of the template forms an
arch 3/8 above the face, allowing installers to
use it as a guide for facing installation. Leave
the template in place to hide the construction
materials behind the template.
Arched Face Thick
Facing Template
NOTE: When installed, there must be a minimum 1/8 gap
between the face and facing.