Avalon Stoves 21 DV Fireplace Indoor Fireplace User Manual


 
Installation (for qualified installers only) 11
© Travis Industries 4040830 100-01143
Corner Installations
A typical 45° installation uses
the minimum framing
dimensions shown in the
illustration to the right (NOTE:
all clearances still apply).
The recommended dimensions
shown to the right allow
additional space, easing gas
line and electrical
connections.
1/2" Standoffs
5-1/2" Min.
6-1/2" Recommended
Min. 1/2"
Clearance
NOTE: do not insert any material into
the 1/2" gap along the front of the
fireplace.
22-1/4" Min.
24-7/8" Recommended
Raised Fireplaces
NOTE: Looking Glass and
Wilmington Faces
require a raised
fireplace - see
"Dimensions" for
details.
The fireplace (and hearth,
if desired) may be placed
on a platform designed to
support the fireplace (125
Lbs.) and vent.
The fireplace may not be
raised so as to place the
ceiling in front of the
fireplace within 57" of the
base of the fireplace.
Raised
Platform
Optional Hearth
Minimum
57"
Ceiling
Fireplace Enclosure
(min. 48")