Avalon Stoves 21 DV Fireplace Indoor Fireplace User Manual


 
22 Installation (for qualified installers only)
© Travis Industries 4040830 100-01143
Facing Requirements
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Face Dimensions
Face Height Width Bottom of Face Installation Notes
Arched Faces 35-1/2” 21-1/8” Flush w base of fireplace Arched top is 25-3/4” radius
Bungalow, T. of L. 35-3/8 21-1/8” Flush w base of fireplace
Vict. Lace 35-1/2” 21-1/8” Flush w base of fireplace
Looking Glass 36-3/4” 23-1/2” 1-1/4” BELOW base of fireplace Cast face is approx. 2” thick
Wilmington 36-3/4” 22-1/8” 1-1/4” BELOW base of fireplace
Facing Under 1” Thick
The facing (combustible
or non-combustible)
must maintain a 1/2
clearance to the sides
and top of the fireplace.
Any material that protrudes
more than 3/4 in front of the
facing is considered a mantel
and must meet the mantel
requirements in this manual.
4-3/4
30-1/4
(approx.)
3-3/8
NOTE: The facing tucks
behind the flanges.
NOTE The facing tucks under the notch at the front
of the fireplace (3/8 above the base of the fireplace).
a
b
c
Recommended Order of Installation We
recommend installing the facing (drywall, tile)
under the notch at the front of the fireplace
(a) - then install the sides and top (b and
c)
Facing Over 1” Thick
Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be
made of non-combustible materials.
NOTE A 3/8" gap above the face is required for face installation and removal.