InRoom Precision AC Tech Data Manual62
50Hz InRoom Electrical Specifications
Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data
Chilled Water (CW) Electrical Data
With Reheat
and
Humidification
Without
Reheat and
Humidification
Compressor Data
Model
Size
Airflow
Pattern
Cooling System
Voltage
(3ph/
50Hz)
FLA FLA LRA RLA
211 U/D
A/G/ACW/
GCW
400
32 14.7 75 10.0
GE 40.9 14.7 75 10.0
311 U/D
A/G/ACW/
GCW
400
48.2 22.0 114 17.3
GE 52.9 26.7 114 17.3
452 U/D
A/G/ACW/
GCW
400
59.6 33.4 100 12.0
GE 72.6 33.4 100 12.0
612 U/D
A/G/ACW/
GCW
400
83.2 44.0 114 17.3
GE 87.9 48.7 114 17.3
862 U/D
A/G/ACW/
GCW
400 102.3 63.1 135 24.5
With Reheat
and
Humidification
Without
Reheat and
Humidification
Model Size
Airflow
Pattern
Cooling
System
Voltage (3ph/
50Hz)
FLA FLA
400 D CW 400 29.5 3.5
400 U CW 400 30.7 4.7
660 U/D CW 400 43.1 8.2
900 U/D CW 400 51.8 9.4
1100 U/D CW 400 64.8 9.4
1500 U/D CW 400 69.5 14.1