APC ACPDX21-86 Air Conditioner User Manual


 
39InRoom Precision AC Tech Data Manual
Information common to both modes PGCW211
Cabinet Size 1
PGCW311
Cabinet Size 2
PGCW452
Cabinet Size 3
PGCW612
Cabinet Size 4
PGCW862
Cabinet Size 5
Connection Sizes
Condenser In/Out - mm (in) 28 (1 1/8) 35 (1 3/8) 35 (1 3/8) 35 (1 3/8) 42 (1 5/8)
Humidifier Supply Line - mm (in) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4) 6 (1/4)
Condensate Drain Line - mm OD (in ID) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4) 21 (3/4)
Fan Information
Number of Fans 1 1 2 2 3
Air Flow - M³/hr (CFM) 125 (4,410) 167 (5,890) 233 (8,240) 323 (11,390) 400 (14,130)
External Static Pressure - Pa (in WC) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2) 50 (0.2)
Sound Power Level - dBA 72.5 77.0 75.8 81.4 80.2
Total Fan Power Consumption - kW (hp) 2.0 (2.7) 2.3 (3.1) 3.6 (4.8) 6.2 (8.3) 7.3 (9.8)
Humidification – Solid State Electrode, Canister
Flush Cycle Automatic Automatic Automatic Automatic Automatic
kg/hr (lb/hr) 8.0 (17.6) 8.0 (17.6) 15.0 (33.1) 15.0 (33.1 15.0 (33.1)
Electric Reheat – Equally Loaded Three (3) phase
Capacity - kW (BTU/hr) - Includes Motor Heat
460 V 12.0 (40982.4) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
230 V 9.0 (30736.8) 18 (61473.6) 18 (61473.6) 27 (92210.4) 27 (92210.4)
Number of Stages 2 3 3 3 3
Downflow Filters - mm Quantities
700 x 508 x 47 G4 1 N/A N/A N/A N/A
1050 x 453 x 47 G4 N/A 2 1 1 1
1050 x 398 x 47 G4 N/A 1 3 4 5
Upflow Filters - mm Quantities
700 x 340 x 47 G4 N/A 1 N/A 1 1
700 x 332 x 47 G4 N/A 1 N/A N/A 1
700 x 502 x 47 G4 N/A 1 1 1 1
700 x 508 x 47 G4 N/A N/A 1 1 2
700 x 516 x 47 G4 1 N/A 1 N/A N/A
Physical Data
Weight - kg (lb) 377 (831) 490 (1080) 608 (1340) 751 (1656) 900 (1984)
Height - mm (in) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95) 1980 (77.95)
Width - mm (in) 1000 (39.37) 1400 (55.11) 1750 (68.90) 2150 (84.65) 2550 (100.39)