APC ACPDX21-86 Air Conditioner User Manual


 
InRoom Precision AC Tech Data Manual12
InRoom Standard Condensers - 60 Hz
* Condenser connections may not represent actual line sizing.
** Dimensions are overall. Electrical enclosure and fan guard are included. Actual fan guard height is 4 in.
Actual electrical enclosure depth is 6.5 in.
InRoom Remote Outdoor Condenser Data, 95°F ambient, 120°F condensation - R407C
InRoom Cabinet Size 1 2 3 4 5
Total Heat Rejection
(THR) BTU/h
96.219 165.496 225.435 279.262 380.436
CFM 8,394 19,325 18,609 17,604 27,963
Fan Diameter - in 19.69 24.80 24.80 24.80 24.80
Voltage Options
208-230/3/60 ACCD76000 ACCD76004 ACCD76008 ACCD76012 ACCD76016
Number of Fans 2 2 2 2 3
Fan RPM (Qty) 1490 1585(1), 1500(1) 1585(1), 1500(1) 1585(1), 1500(1) 1585(2), 1500(1)
Motor HP (Qty) 1.23 Hp(2) 3.58(1), 3.85(1) 3.58(1), 3.85(1) 3.58(1), 3.85(1) 3.58(2), 3.85(1)
Electrical Data
FLA 8.6 19.7 19.7 19.7 29.1
MCA 9.8 22.1 22.1 22.1 31.5
MFS 15 30 30 30 40
460-480/3/60 ACCD76010 ACCD76005 ACCD76009 ACCD76013 ACCD76017
Number of Fans 2 2 2 2 3
Fan RPM (Qty) 1450(1), 1570(1)1650(1), 1500(1) 1650(1), 1500(1) 1650(1), 1500(1) 1650(2), 1500(1)
Motor HP (Qty) 1.34(1), 1.64(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1) 3.90(2), 3.85(1)
Electrical Data
FLA 3.9 9.5 9.5 9.5 14.57
MCA 4.3 10.7 10.7 10.7 15.85
MFS 15 15 15 15 20
575-600/3/60 ACCD76022 ACCD76023 ACCD76024 ACCD76025 ACCD76026
Number of Fans 2 2 2 2 3
Fan RPM (Qty) 1450(1), 1570(1)1650(1), 1500(1) 1650(1), 1500(1) 1650(1), 1500(1) 1650(2), 1500(1)
Motor HP (Qty) 1.34(1), 1.64(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1) 3.90(2), 3.85(1)
Electrical Data
FLA 3.4 8.0 8.0 8.0 12.3
MCA 37 9.0 9.0 9.0 13.4
MFS 15.0 15.0 15.0 15.0 15.0
Refrigerant Connections*
Hot Gas Line - in 1 1/8 OD 1 1/8 OD 1 3/8 OD 1 3/8 OD 1 5/8 OD
Liquid Line - in 7/8 OD 7/8 OD 1 1/8 OD 1 1/8 OD 1 3/8 OD
Physical Data**
Dimensions -HxWxD in 35.5x32.75x76 48x108.5x48.25 48x108.5x48.25 48x108.5x48.25 48x155.5x48.25
Approximate Weight - lb. 240 455 495 555 835