APC ACPA4000 Air Conditioner User Manual


 
13NetworkAIR ACPA4000
Relays and Contacts
Overview
The controller board provides connectors for output relays and input contacts. The connectors can be
used with any dry-contact sensors. The connectors are designed to monitor circuits that have no voltage
potential of their own. Connecting the contact or relay to any circuit other than a dry closure connector
may result in damage to the main control board.
You can connect any normally open (NO) or normally closed (NC) dry contact sensor, including:
magnetic contact switches
window foil
tamper switches
heat detectors
• water sensors
pressure sensors
smoke detectors
Output relays
This figure shows the four positions on the output relay connector and provides the individual pin
assignments for each position.
Note: The terminal block
accepts wire sizes from 1.6mm
2
(14AWG) to 0.4mm
2
(26AWG).
Electrical Hazard: Control board connections should be made only to Class 2 circuits.
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
na0342a
Position 1
Position 3
Position 4
Position 2