A.O. Smith DB/DW-720-1810 Boiler User Manual


 
10
TABLE 5
Multipliers To Be Used With Table 1 When Applying The
Gravity Factor To Other Than .60 Specific Gravity
Specific Specific
Gravity Multiplier Gravity Multiplier
.35 1.31 1.00 .78
.40 1.23 1.10 .74
.45 1.16 1.20 .71
.50 1.10 1.30 .68
.55 1.04 1.40 .66
*.60 (Nat.) 1.00 *1.50 (Prop.) .63
.65 .96 1.60 .61
.70 .93 1.70 .59
.75 .90 1.80 .58
.80 .87 1.90 .56
.85 .84 *2.00 (Butane) .55
.90 .82 2.10 .54
*Use these correction factors if exact specific gravity of the gas is not known.
PURGING
Gas line purging is required with new piping or systems in which
air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS
EXPERIENCED IN THIS TYPE OF GAS SERVICE TO AVOID RISK
OF FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT
ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN
OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL
SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED.
BEFORE PLACING THE BOILER IN OPERATION, CHECK FOR
GAS LEAKAGE. Use soap and water solution or other material
acceptable for the purpose in locating gas leaks. DO NOT USE
MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION FOR THIS PURPOSE.
1. CORRECT GAS
Make sure the gas on which the boiler will operate is the same as
that specified on the boiler rating plate. Do not install the boiler if
equipped for a different type gas, consult your gas supplier. These
boilers are designed to operate on natural gas only.
2A. SIZING GAS SUPPLY LINE (For single boiler installations
and for installations of multiples of two or three of same size
boilers).
Use table 1, which is taken from ANSI booklet Z223.1,
NATIONAL
FUEL GAS CODE, and/or CAN/CSA-B149.1-00 to size iron pipe
or equivalent gas supply line. Table 4 is based on a pressure drop
of 0.3 inches of water and a specific gravity of 0.60 which is
approximately for natural gas. (LP gas has an S.G. of about 1.53).
If the service pressure is five inches water column or less, use one
pipe size larger than specified in table 1 in order to minimize pressure
drop in the line.
2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers
of same size or for multiple installations of two or more mixed
sizes).
Capacities in cubic feet per hour of 0.60 specific gravity gas for
different sizes and lengths are shown in table 4. No additional
allowance is necessary for an ordinary number of fittings.
Where it is necessary to use more than the average number of
pipe fittings i.e. elbows, tees, and valves in gas supply line, use a
pipe larger than specified to compensate for increased pressure
drop.
TABLE 4
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (BASED UPON A PRESSURE DROP OF
0.3 INCH WATER COLUMN AND 0.6 SPECIFIC GRAVITY GAS)
Length in Feet (Meters) Nominal Iron Pipe Size, Inches (NPT)
From Gas Meter 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
10 (3) 132 278 520 1,050 1,600 3,050 4,800 8,500 17,500
20 (6) 92 190 350 730 1,100 2,100 3,300 5,900 12,000
30 (9) 73 152 285 590 890 1,650 2,700 4,700 9,700
40 (12) 63 130 245 500 760 1,450 2,300 4,100 8,300
50 (15) 56 115 215 440 670 1,270 2,000 3,600 7,400
60 (18) 50 105 195 400 610 1,150 1,850 3,250 6,800
70 (21) 46 96 180 370 560 1,050 1,700 3,000 6,200
80 (24) 43 90 170 350 530 990 1,600 2,800 5,800
90 (27) 40 84 160 320 490 930 1,500 2,600 5,400
100 (30) 38 79 150 305 460 870 1,400 2,500 5,100
125 (38) 34 72 130 275 410 780 1,250 2,200 4,500
150 (46) 31 64 120 250 380 710 1,130 2,000 4,100
175 (53) 28 59 110 225 350 650 1,050 1,850 3,800
200 (61) 26 55 100 210 320 610 980 1,700 3,500
*The heating value of natural gas is approximately 1050 Btu/ft³.
Propane (L.P.) gas has a heating value of approximately 2500 Btu/ft³.