A.O. Smith 317443-000 Water Heater User Manual


 
13
1. 1 square inch per 3000 Btu/hr (700 mm
2
per kW) of the total
input rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
FIGURE 6.
The conned space shall be provided with two permanent horizontal
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The horizontal ducts shall communicate directly with the
outdoors. See Figure 6.
Each duct opening shall have a minimum free area of 1 square inch
per 2,000 Btu/hr (1100 mm
2
per kW) of the aggregate input rating of
all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area
as the free area of the openings to which they connect. The minimum
dimension of rectangular air ducts shall be not less than 3 inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 7.
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. See Figure 7.
Each opening shall communicate directly with an additional room(s)
of sufcient volume so that the combined volume of all spaces
meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch per
1,000 Btu/hr (1100 mm
2
per kW) of the aggregate input rating of all
appliances installed in the enclosure. Each opening shall not be
less than 100 square inches (645 cm
2
).