Unit Weights
TABLE 23 – UNIT WEIGHTS
Model 050 051 060 061
Basic Unit* 7433 7433 7800 7819
Economizers
No Outside Air 240 240 240 240
25% Outside Air Fixed Position Maual Damper 446 446 446 446
25% Outside Air 2 Position Actuated Damper 476 476 476 476
Full Modulation with Minimum Position 476 476 476 476
Power Exhausts
Fan, Motor, Modulating Damper and Hood 501 501 501 501
Fan, Motor, VFD, Barometric Damper and Hood 506 506 506 506
Gas Heat
375 MBH 162 162 162 162
750 MBH 324 324 324 324
1125 MBH (Bottom Discharge) 486 486 486 486
Options
Open Perimeter Curb 544 544 544 544
Condenser Coil Wire Guard 64 64 64 64
Copper Evaporator Coils (additional) 312 312 416 416
Copper Condenser Coils (additional) 516 516 773 773
12” Rigid Filters (additional) 319 319 319 319
*Unit includes FC fan w/ 20 hp motor, VFD and 2” throwaway fi lters
X
339
Y
92
A
B C
D
Condenser
Coil End
Center of Gravity
TABLE 24 – UNIT CENTER OF GRAVITY
Model
050 051
XYXY
Basic Unit 184.1 50.2 184.1 50.2
Basic Unit w/ Econ. 191.0 49.9 191.0 49.9
Basic Unit w/ Econ. & Heating 187.4 50.0 187.4 50.0
Basic Unit w/ Econ. & Heating & Power Exhaust 194.9 49.5 194.9 49.5
Model
060 061
XYXY
Basic Unit 179.8 49.9 179.6 50.0
Basic Unit w/ Econ. 186.7 49.7 186.5 49.7
Basic Unit w/ Econ. & Heating 183.5 49.8 183.2 49.8
Basic Unit w/ Econ. & Heating & Power Exhaust 190.9 49.3 190.7 49.3