York HFC-410A Air Conditioner User Manual


 
FORM 100.50-EG5 (108)
35
JOHNSON CONTROLS
CURB LAYOUT DRAWING
LD08297
FIG. 6 – GENERAL ARRANGEMENT DRAWING
NOTES:
1. Unit must be installed square and level.
2. Curb con guration for “bottom” return and “bottom” supply.
3, These drawings are not intended as construction documents for the eld-fabricated roof curbs. YORK will not be responsible for the unit
t-up, leak integrity, or sound level for installation using eld-fabricated roof curbs.
4. The YPAL unit does not have a base pan under the condensing section of the unit. Field-fabricated roof curbs must have a cap on the top
of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped away from the supply-
duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
229.56
66.08
333.69
41.19
71.83
66.19
21.00
35.10
14.00
84.50
1.75
TYP
SUPPLY
RETURN