York 291627-YTG-B-0807 Air Conditioner User Manual


 
291627-YTG-B-0807
8 Unitary Products Group
TABLE 3: DNH030 COOLING CAPACITIES - 2-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
750 CFM 875 CFM 1,000 CFM 1,125 CFM 1,250 CFM
WB °F WB °F WB °F WB °F WB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
85 °F
NET CAP.
MBH
27.2 26.8 24.1 24.0 28.5 28.1 25.3 25.2 29.8 29.4 26.4 26.4 29.4 29.0 26.1 26.0 29.0 28.6 25.7 25.6
TOTAL POWER
INPUT kW
2.35 2.34 2.32 2.32 2.40 2.39 2.37 2.36 2.44 2.43 2.41 2.40 2.52 2.51 2.49 2.48 2.60 2.59 2.57 2.56
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 17.3 22.2 24.1 24.0 19.4 24.9 25.3 25.2 21.6 27.6 26.4 26.4 22.4 28.1 26.1 26.0 23.3 28.6 25.7 25.6
83 15.1 20.1 23.0 23.9 16.9 22.4 24.7 25.1 18.7 24.7
26.4 26.4 19.1 25.1 26.1 26.0 19.6 25.6 25.7 25.6
80 13.0 17.9 20.8 21.7 14.4 19.8 23.0 24.0 15.8 21.7 25.2 26.3 15.8 21.8 25.3
26.0 15.8 21.8 25.4 25.6
77 10.9 15.8 18.7 19.6 11.8 17.3 20.5 21.5 12.8 18.8 22.3 23.4 12.5 18.5 22.0 22.7 12.1 18.1 21.6 21.9
74 8.7 13.7 16.5 17.5 9.3 14.8 18.0 19.0 9.9 15.9 19.4 20.5 9.1 15.1 18.7 19.3 8.4 14.4 17.9 18.2
71 - 11.5 14.4 15.3 - 12.3 15.5 16.5 - 13.0 16.5 17.6 - 11.8 15.3 16.0 - 10.7 14.2 14.4
68 - 9.4 12.3 13.2 - 9.7 12.9 13.9 - 10.1 13.6 14.7 - 8.5 12.0 12.7 - 6.9 10.5 10.7
95 °F
NET CAP.
MBH
24.0 23.0 21.1 20.5 26.6 25.5 23.3 22.7 29.2 28.0 25.6 24.9 29.1 27.9 25.5 24.8 29.0 27.7 25.4 24.7
TOTAL POWER
INPUT kW
2.56 2.54 2.50 2.50 2.60 2.58 2.54 2.54 2.65 2.63 2.58 2.58 2.74 2.71 2.67 2.67 2.82 2.80 2.76 2.75
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 16.1 20.7 21.1 20.5 18.8 24.2 23.3 22.7 21.6 27.6 25.6 24.9 22.6 27.7 25.5 24.8 23.7 27.7 25.4 24.7
83 14.0 18.5
21.1 20.5 16.3 21.6 23.3 22.7 18.7 24.7 25.6 24.9 19.3 25.4 25.5 24.8 19.9 26.2 25.4 24.7
80 11.8 16.4 19.2 18.6 13.8 19.1 22.4 21.7 15.7 21.8
25.6 24.7 16.0 22.1 25.5 24.7 16.2 22.4 25.4 24.7
77 9.7 14.3 17.1 16.5 11.3 16.6 19.9 19.1 12.8 18.9 22.7 21.8 12.7 18.8 22.2 21.4 12.5 18.7 21.7 21.0
74 7.6 12.1 15.0 14.3 8.7 14.0 17.4 16.6 9.9 16.0 19.8 18.9 9.3 15.5 18.9 18.1 8.8 15.0 17.9 17.2
71 - 10.0 12.8 12.2 - 11.5 14.8 14.1 - 13.1 16.9 16.0 - 12.2 15.5 14.8 - 11.3 14.2 13.5
68 - 7.8 10.7 10.0 - 9.0 12.3 11.6 - 10.1 13.9 13.1 - 8.8 12.2 11.4 - 7.5 10.5 9.8
105 °F
NET CAP.
MBH
22.8 20.8 19.4 19.0 25.1 22.9 21.4 20.9 27.4 25.0 23.3 22.8 27.5 25.1 23.4 22.9 27.7 25.2 23.5 23.0
TOTAL POWER
INPUT kW
2.76 2.72 2.68 2.68 2.81 2.77 2.73 2.72 2.85 2.81 2.77 2.77 2.94 2.90 2.86 2.85 3.03 2.99 2.95 2.94
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 16.0 19.6 19.4 19.0 18.4 22.3 21.4 20.9 20.8 24.9 23.3 22.8 22.3 25.0 23.4 22.9 23.7 25.2 23.5 23.0
83 13.9 18.0
19.4 19.0 15.9 20.6 21.4 20.9 17.9 23.2 23.3 22.8 18.9 23.8 23.4 22.9 20.0 24.5 23.5 23.0
80 11.8 15.8 18.2 17.5 13.4 18.0 20.8 20.0 15.0 20.2
23.3 22.4 15.6 21.0 23.4 22.7 16.2 21.8 23.5 23.0
77 9.6 13.7 16.1 15.4 10.9 15.5 18.2 17.4 12.1 17.3 20.4 19.5 12.3 17.7 20.1 19.4 12.5 18.1 19.8 19.2
74 7.5 11.6 13.9 13.2 8.3 13.0 15.7 14.9 9.2 14.4 17.5 16.6 9.0 14.4 16.8 16.1 8.8 14.4 16.1 15.5
71 - 9.4 11.8 11.1 - 10.5 13.2 12.4 - 11.5 14.6 13.7 - 11.1 13.4 12.7 - 10.7 12.3 11.8
68 - 7.3 9.7 9.0 - 7.9 10.7 9.9 - 8.6 11.6 10.8 - 7.8 10.1 9.4 - 6.9 8.6 8.1
115 °F
NET CAP.
MBH
21.6 18.6 17.7 17.4 23.6 20.4 19.4 19.0 25.6 22.1 21.0 20.6 26.0 22.4 21.3 20.9 26.4 22.7 21.6 21.3
TOTAL POWER
INPUT kW
2.96 2.90 2.86 2.86 3.01 2.95 2.91 2.91 3.06 3.00 2.96 2.95 3.15 3.09 3.05 3.04 3.24 3.18 3.13 3.13
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 16.0 18.6 17.7 17.4 18.0 20.4 19.4 19.0 20.1 22.1 21.0 20.6 21.9 22.4 21.3 20.9 23.7 22.7 21.6 21.3
83 13.8 17.4
17.7 17.4 15.5 19.5 19.4 19.0 17.2 21.6 21.0 20.6 18.6 22.2 21.3 20.9 20.0 22.7 21.6 21.3
80 11.7 15.3 17.2 16.4 13.0 17.0 19.1 18.3 14.3 18.7
21.0 20.1 15.3 20.0 21.3 20.7 16.2 21.2 21.6 21.3
77 9.5 13.1 15.0 14.3 10.5 14.4 16.6 15.7 11.4 15.8 18.1 17.2 11.9 16.6 18.0 17.4 12.5 17.5 17.9 17.5
74 7.4 11.0 12.9 12.2 7.9 11.9 14.0 13.2 8.5 12.8 15.2 14.3 8.6 13.3 14.7 14.0 8.8 13.8 14.2 13.8
71 - 8.9 10.8 10.0 - 9.4 11.5 10.7 - 9.9 12.3 11.4 - 10.0 11.4 10.7 - 10.1 10.5 10.1
68 - 6.7 8.6 7.9 - 6.9 9.0 8.2 - 7.0 9.3 8.4 - 6.7 8.0 7.4 - 6.3 6.7 6.4
125 °F
NET CAP.
MBH
20.4 16.4 16.1 15.9 22.1 17.8 17.4 17.2 23.8 19.1 18.7 18.5 24.4 19.7 19.2 19.0 25.1 20.2 19.8 19.5
TOTAL POWER
INPUT kW
3.16 3.09 3.05 3.04 3.22 3.14 3.10 3.09 3.27 3.19 3.15 3.14 3.36 3.28 3.23 3.23 3.45 3.36 3.32 3.31
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 15.9 14.6 16.1 15.9 17.6 18.5 17.4 17.2 19.4 19.3 18.7 18.5 21.6 19.8 19.2 19.0 23.7 20.2 19.8 19.5
83 13.7 16.9
16.1 15.9 15.1 18.4 17.4 17.2 16.5 20.0 18.7 18.5 18.2 20.5 19.2 19.0 20.0 21.0 19.8 19.5
80 11.6 14.7
16.1 15.4 12.6 15.9 17.4 16.6 13.6 17.1 18.7 17.8 14.9 18.9 19.2 18.7 16.3 20.6 19.8 19.5
77 9.5 12.6 14.0 13.2 10.1 13.4 14.9 14.0 10.6 14.2 15.8 14.9 11.6 15.5 15.9 15.3 12.5 16.9 16.0 15.8
74 7.3 10.4 11.9 11.1 7.5 10.9 12.4 11.5 7.7 11.3 12.9 11.9 8.3 12.2 12.6 12.0 8.8 13.2 12.3 12.1
71 - 8.3 9.7 8.9 - 8.3 9.8 9.0 - 8.4 10.0 9.0 - 8.9 9.3 8.7 - 9.5 8.6 8.4
68 - 6.2 7.6 6.8 - 5.8 7.3 6.5 - 5.4 7.0 6.1 - 5.6 5.9 5.4 - 5.7 4.9 4.6
1. These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY