York 291627-YTG-B-0807 Air Conditioner User Manual


 
291627-YTG-B-0807
10 Unitary Products Group
TABLE 5: DNH042 COOLING CAPACITIES - 3-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,050 CFM 1,225 CFM 1,400 CFM 1,575 CFM 1,750 CFM
WB °F WB °F WB °F WB °F WB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
85 °F
NET CAP.
MBH
38.6 38.4 34.0 33.3 42.1 41.8 37.0 36.3 45.5 45.3 40.1 39.2 45.3 45.0 39.9 39.1 45.1 44.8 39.7 38.9
TOTAL POWER
INPUT kW
4.05 3.83 3.95 3.91 4.01 3.79 3.92 3.87 3.98 3.76 3.88 3.84 4.12 3.90 4.02 3.98 4.27 4.03 4.16 4.12
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 25.5 32.6 34.0 33.3 28.9 36.8 37.0 36.3 32.2 41.0 40.1 39.2 34.4 42.9 39.9 39.1 36.6 44.8 39.7 38.9
83 22.5 29.6
34.0 33.3 25.4 33.3 37.0 36.3 28.2 36.9 40.1 39.2 29.8 38.9 39.9 39.1 31.4 40.9 39.7 38.9
80 19.6 26.6 31.9 31.9 21.8 29.7 35.6 35.6 24.1 32.8 39.3
39.2 25.1 34.3 39.5 39.1 26.2 35.7 39.7 38.9
77 16.6 23.6 28.9 28.9 18.3 26.2 32.1 32.0 20.0 28.7 35.2 35.2 20.5 29.6 34.8 34.4 21.0 30.5 34.5 33.6
74 13.6 20.7 25.9 25.9 14.7 22.7 28.5 28.5 15.9 24.7 31.1 31.1 15.8 25.0 30.2 29.8 15.8 25.3 29.2 28.4
71 - 17.7 22.9 22.9 - 19.1 25.0 24.9 - 20.6 27.1 27.0 - 20.3 25.5 25.1 - 20.1 24.0 23.2
68 - 14.7 19.9 19.9 - 15.6 21.5 21.4 - 16.5 23.0 22.9 - 15.7 20.9 20.5 - 14.9 18.8 18.0
105 °F
NET CAP.
MBH
36.8 36.2 32.1 31.6 40.2 39.5 35.1 34.5 43.6 42.9 38.1 37.5 43.4 42.7 37.9 37.3 43.3 42.6 37.8 37.2
TOTAL POWER
INPUT kW
4.45 4.20 4.29 4.28 4.41 4.17 4.25 4.24 4.37 4.13 4.21 4.20 4.51 4.26 4.34 4.33 4.65 4.39 4.48 4.46
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 25.5 32.1 32.1 31.6 28.9 36.2 35.1 34.5 32.2 40.4 38.1 37.5 34.6 41.5 37.9 37.3 36.9 42.6 37.8 37.2
83 22.5 29.1
32.1 31.6 25.3 32.7 35.1 34.5 28.1 36.3 38.1 37.5 29.9 38.5 37.9 37.3 31.7 40.7 37.8 37.2
80 19.5 26.1 30.6 30.4 21.8 29.2 34.2 33.9 24.1 32.2 37.8
37.5 25.3 33.8 37.8 37.3 26.5 35.4 37.8 37.2
77 16.5 23.1 27.7 27.4 18.3 25.6 30.7 30.4 20.0 28.1 33.7 33.4 20.6 29.2 33.1 32.7 21.3 30.2 32.6 32.0
74 13.5 20.1 24.7 24.4 14.7 22.1 27.1 26.8 15.9 24.0 29.6 29.3 16.0 24.5 28.5 28.0 16.1 25.0 27.4 26.8
71 - 17.1 21.7 21.4 - 18.5 23.6 23.3 - 19.9 25.5 25.2 - 19.9 23.8 23.4 - 19.8 22.2 21.6
68 - 14.1 18.7 18.4 - 15.0 20.1 19.8 - 15.9 21.5 21.1 - 15.2 19.2 18.7 - 14.6 16.9 16.3
115 °F
NET CAP.
MBH
35.4 33.7 29.9 29.5 38.7 36.8 32.7 32.2 42.1 40.0 35.5 35.0 41.8 39.7 35.2 34.8 41.4 39.4 35.0 34.5
TOTAL POWER
INPUT kW
4.80 4.64 4.73 4.72 4.78 4.62 4.71 4.70 4.75 4.59 4.68 4.67 4.88 4.71 4.80 4.80 5.00 4.83 4.93 4.92
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 24.8 31.0 29.9 29.5 28.2 34.9 32.7 32.2 31.6 38.7 35.5 35.0 34.0 39.1 36.2 34.8 36.3 39.4 35.0 34.5
83 21.8 28.0
29.9 29.5 24.7 31.6 32.7 32.2 27.5 35.3 35.5 35.0 29.3 36.8 35.2 34.8 31.1 38.4 35.0 34.5
80 18.8 25.0 28.4 28.1 21.1 28.1 31.9 31.6 23.5 31.2 35.4
35.0 24.7 32.8 35.2 34.8 25.9 34.4 35.0 34.5
77 15.8 22.0 25.4 25.1 17.6 24.6 28.3 28.0 19.4 27.1 31.3 30.9 20.0 28.2 30.5 30.1 20.7 29.2 29.7 29.3
74 12.8 19.0 22.4 22.1 14.1 21.0 24.8 24.5 15.3 23.0 27.2 26.9 15.4 23.5 25.9 25.5 15.5 24.0 24.5 24.1
71 - 16.0 19.4 19.1 - 17.5 21.3 21.0 - 18.9 23.1 22.8 - 18.9 21.2 20.8 - 18.8 19.3 18.8
68 - 13.1 16.4 16.1 - 14.0 17.7 17.4 - 14.9 19.0 18.7 - 14.2 16.6 16.2 - 13.6 14.1 13.6
125 °F
NET CAP.
MBH
34.0 31.1 27.6 27.3 37.3 34.1 30.3 30.0 40.6 37.1 32.9 32.6 40.1 36.6 32.5 32.2 39.6 36.2 32.1 31.8
TOTAL POWER
INPUT kW
5.16 5.08 5.18 5.17 5.14 5.07 5.16 5.16 5.13 5.05 5.15 5.14 5.24 5.17 5.26 5.26 5.36 5.28 5.38 5.37
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 24.1 29.9 27.6 27.3 27.6 33.5 30.3 30.0 31.0 37.1 32.9 32.6 33.4 36.6 32.5 32.2 35.7 36.2 32.1 31.8
83 21.1 26.9
27.6 27.3 24.0 30.6 30.3 30.0 26.9 34.3 32.9 32.6 28.7 35.2 32.5 32.2 30.5 36.2 32.1 31.8
80 18.1 23.9 26.1 25.9 20.5 27.1 29.5 29.2 22.8 30.2
32.9 32.6 24.1 31.8 32.5 32.2 25.3 33.4 32.1 31.8
77 15.1 21.0 23.1 22.9 17.0 23.5 26.0 25.7 18.8 26.1 28.8 28.5 19.4 27.2 27.9 27.5 20.1 28.2 26.9 26.6
74 12.1 18.0 20.1 19.9 13.4 20.0 22.5 22.2 14.7 22.0 24.8 24.4 14.8 22.5 23.2 22.9 14.9 23.0 21.7 21.3
71 - 15.0 17.2 16.9 - 16.4 18.9 18.6 - 17.9 20.7 20.3 - 17.9 18.6 18.2 - 17.8 16.5 16.1
68 - 12.0 14.2 13.9 - 12.9 15.4 15.1 - 13.8 16.6 16.3 - 13.2 13.9 13.6 - 12.6 11.2 10.9
125 °F
NET CAP.
MBH
32.7 28.6 25.4 25.2 35.9 31.4 27.9 27.7 39.1 34.2 30.4 30.2 38.4 33.6 29.8 29.6 37.7 33.0 29.2 29.1
TOTAL POWER
INPUT kW
5.50 5.50 5.60 5.60 5.50 5.50 5.60 5.60 5.50 5.50 5.60 5.60 5.60 5.60 5.70 5.70 5.70 5.70 5.80 5.80
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 23.4 28.9 25.4 25.2 26.9 32.2 27.9 27.7 30.4 35.5 30.4 30.2 32.8 34.2 29.8 29.6 35.2 33.0 29.2 29.1.
83 20.4 25.9
25.4 25.2 23.4 29.6 27.9 27.7 26.3 33.3 30.4 30.2 28.1 33.6 29.8 29.6 29.9 33.9 29.2 29.1
80 17.4 22.9 23.9 23.6 19.8 26.0 27.2 26.9 22.2 29.2 30.5
30.2 23.5 30.8 29.9 29.6 24.7 32.4 29.2 29.1
77 14.4 19.9 20.9 20.6 16.3 22.5 23.7 23.3 18.2 25.1 26.4 26.1 18.8 26.2 25.2 25.0 19.5 27.2 24.0 23.8
74 11.5 16.9 17.9 17.6 12.8 18.9 20.1 19.8 14.1 21.0 22.3 22.0 14.2 21.5 20.6 20.3 14.3 22.0 18.8 18.6
71 - 13.9 14.9 14.6 - 15.4 16.6 16.3 - 16.9 18.3 17.9 - 16.9 15.9 15.7 - 16.8 13.6 13.4
68 - 10.9 11.9 11.6 - 11.9 13.0 12.7 - 12.8 14.2 13.8 - 12.2 11.3 11.0 - 11.6 8.4 8.2
1. These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY