York 291627-YTG-B-0807 Air Conditioner User Manual


 
291627-YTG-B-0807
16 Unitary Products Group
TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 & 460 VOLTS
1
MODEL #
DNH
(Cooling/
Heating)
MTR
SPD
EXTERNAL STATIC PRESSURE - IWG
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
030
HI------1080504999483917463836442728425------
MED 999 345 949 331 899 318 850 304 778 287 707 269 - - - - - - - - - -
LOW898335815300732265----------------
036
HI----------1436735134570511896671032 628 - - - -
MED - - - - 1490 652 1422 625 1339 602 1257 578 1174 555 1049 526 953 497 - - - -
LOW 1387 582 1330 569 1274 555 1217 542 1148 520 1079 497 1010 475 - - - - - - - -
042
HI - - - - 1695 821 1618 796 1527 766 1436 735 1345 705 1189 667 - - - - - -
MED 1625 707 1557 680 1490 652 1422 625 1339 602 1257 578 1174 555 - - - - - - - -
LOW 1387 582 1330 569 1274 555 1217 542 1148 520 1079 497 - - - - - - - - - -
048
HI 1768 844 1720 824 1672 804 1613 779 1554 754 1484 727 1414 700 1290 663 - - - - - -
MED 1641 754 1594 730 1547 707 1495 683 1442 660 1379 633 1316 606 - - - - - - - -
LOW 1550 663 1513 645 1477 626 1428 608 1378 590 1324 564 1270 539 - - - - - - - -
060
(only
575 volts)
HI 2326 1280 2283 1230 2200 1200 2123 1163 2045 1125 1953 1085 1860 1045 1698 990 1535 935 - - - -
MED 2159 1125 2098 1090 2036 1055 1967 1020 1897 985 1814 945 1731 905 1578 582 - - - - - -
LOW 1937 990 1892 983 1846 935 1785 908 1723 880 1655 843 1587 805 - - - - - - - -
060
(3 tube)
(only 230 &
460 volts)
HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 1500 610 1500 680 1500 750 1500 820 1500 890
060
(4 & 5 tube)
(only 230 &
460 volts)
HEAT 1700 390 1700 443 1700 497 1700 550 1700 620 1700 690 1700 760 1700 830 1700 900 1700 970 - -
060
(factory
setting)
(only 230 &
460 volts)
COOL 1800 460 1800 515 1800 570 1800 625 1800 690 1800 755 1800 820 1800 962 1800 1105 - - - -
060
(field
setting)
(only 230 &
460 volts)
COOL 2000 640 2000 700 2000 760 2000 820 2000 928 2000 1035 - - - - - - - - - -
1. Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to
Tables 12 and 13.
TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE 2-1/2 - 3 TON (DNH030 - 036)
1
DESCRIPTION
RESISTANCE, IWG
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600
WET EVAPORATOR COIL .01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09
ECONOMIZER
2
.00 .00 .00 .01 .01 .01 .01 .02 .03 .04 .05 .06
FILTER FRAME KIT .01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20
1. Deduct these resistance values from the available external static pressure shown in Tables 8, 9, 10, and 11.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.