TABLE 14: ELECTRICAL DATA
MODEL
DNH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN. MAX. RLA LRA
030 208/230-3-60 187 253 8.6 55 1.1 2.6 14.5 20 20 .96 75
030 460-3-60 414 504 4.3 27 0.6 1.4 7.4 15 15 .96 75
036 208/230-3-60 187 253 11.4 77 1.1 3.5 18.9 25 25 .96 75
036 460-3-60 414 504 5.7 39 0.6 1.8 9.5 15 15 .96 75
042 208/230-3-60 187 253 13.9 88 1.3 3.5 22.2 30 30 .96 75
042 460-3-60 414 504 6.4 44 0.7 1.8 10.5 15 15 .96 75
048 208/230-3-60 187 253 13.0 93 1.9 4.2 22.4 30 30 .96 75
048 460-3-60 414 504 6.4 46.5 1.0 2.1 11.1 15 15 .96 75
060 208/230-3-60 187 253 19.3 123 1.9 9.4 32.9 45 45 .96 75
060 460-3-60 414 504 10.0 62 1.0 4.7 16.0 20 20 .96 75
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.