York 291627-YTG-B-0807 Air Conditioner User Manual


 
291627-YTG-B-0807
28 Unitary Products Group
TYPICAL WIRING DIAGRAM NOTES
(SEE FIGURES 14 THRU 17)
1. All field wiring to be accomplished following city, local
and/or national codes in effect at time of installation of
this unit.
2. Caution: Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper and
dangerous operation. If any of the wire as supplied with
this unit must be removed it must be replaced with type
105°C, 600V wire or equivalent clearly renumbered for
identification. Verify proper operation after servicing.
3. Motors inherently protected.
4. Factory wired for 460V operation.
5. See unit nameplate for maximum fuse size and/or circuit
breaker size and minimum circuit ampacity.
6. If both LR and ASCT are present, wire 801/BL and 805/
BL are connected to ASCT-3. If only LR is present wire
801/BL and 805/BL are connected to M1 coil. If only
ASCT is present wire 202/Y is connected to ASCT-3. If
neither LR or ASCT are present, wire 202/Y is connected
to M1 coil as shown.
7. Shunt contact also used with crankcase heater.
(optional)
8. Unit factory wired for low or medium speed indoor blower
operation. To change motor speed, connect speed tap
wires from indoor blower motor, per Detail A (Figure 19).
Tape unused speed tap wires to prevent shorting and
secure.
9. Select indoor blower speed to remain within the temper-
ature rise range on the nameplate in heating.
FIGURE 18 - TYPICAL WIRING DIAGRAM LEGEND
Open all disconnects before servicing this unit.
LEGEND
ALS AUXILARY LIMIT SWITCH
ASCT ANTI-SHORT CYCLE TIMER (OPTIONAL)
BR BLOWER RELAY
CB CIRCUIT BREAKER
CCH CRANK CASE HEATER (OPTIONAL)
COMPR COMPRESSOR
DM DRAFT MOTOR
FCB FAN CONTROL BOARD
GND GROUND
FS FREEZE STAT SWITCH (OPTIONAL)
HP HIGH PRESSURE SWITCH OPENS @ 380 PSIG
IDFAN INDOOR FAN MOTOR
LP LOW PRESSURE SWITCH OPENS @ 7 PSIG
LS LIMIT SWITCH
LR LOCK OUT RELAY (OPTIONAL)
M1 CONTACTOR, COMPR. AND OD FAN
ODFAN OUTDOOR FAN MOTOR
PS PRESSURE SWITCH
RC1 / RC2 COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
RS ROLLOUT SWITCH
TB4 TERMINAL BLOCK
T1 TRANSFORMER, 24V, 230V
T2 TRANSFORMER, 460V / 575V