York 251934-YTG-J-0910 Air Conditioner User Manual


 
251934-YTG-J-0910
Johnson Controls Unitary Products 85
300
(25)
208-3-60 38.0 42.9 304 267 59.4 63 4.5 28.0 0.0
None - - - 134.9 175
E18 13.5 1 37.5 134.9 175
E36 27.0 2 74.9 134.9 175
E54 40.6 2 112.7 175.9 200
E72 54.1 2 150.2 185.2 200
230-3-60 38.0 42.9 304 267 59.4 63 4.3 26.0 0.0
None - - - 132.5 175
E18 18.0 1 43.3 132.5 175
E36 36.0 2 86.6 140.8 175
E54 54.0 2 129.9 162.4 175
E72 72.0 2 173.2 205.7 225
460-3-60 18.9 18.5 162.6 130 29.5 29 2.2 13.0 0.0
None---62.280
E18 18.0 1 21.7 62.2 80
E36 36.0 2 43.3 70.4 80
E54 54.0 2 65.0 81.2 90
E72 72.0 2 86.6 102.9 110
575-3-60 15.1 15.3 135.9 114 23.7 24 1.7 10.3 0.0
None---50.260
E18 18.0 1 17.3 50.2 60
E36 36.0 2 34.6 56.2 60
E54 54.0 2 52.0 64.8 70
E72 72.0 2 69.3 82.2 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF180-300 - Standard Drive Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA FLA FLA Model kW Stages Amps
C1 C2 C1 C2 C1 C2