115°F 125°F
4375
77 206.1 20.8 80.0 70.9 52.9 - - - 190.0 22.6 66.6 63.7 46.3 - - -
72 190.8 20.5 121.1 103.1 85.1 67.1 - - 175.7 22.2 113.6 96.1 78.7 61.2 - -
67 175.5 20.2 162.1 135.3 117.3 99.3 81.3 - 161.5 21.9 160.3 128.5 111.0 93.5 76.0 -
62 167.3 20.0 167.3 166.3 136.4 118.4 100.5 82.5 157.2 21.8 157.2 155.7 124.1 106.6 89.1 71.6
5250
77 213.6 20.8 101.5 80.1 58.6 - - - 196.9 22.5 94.7 73.3 51.9 - - -
72 197.7 20.5 137.2 115.8 94.3 72.8 - - 182.2 22.2 130.8 109.4 88.0 66.7 - -
67 181.8 20.1 172.9 151.5 130.0 108.5 87.1 - 167.5 21.8 166.9 145.5 124.2 102.8 81.4 -
62 173.3 20.0 173.3 172.7 151.2 129.8 108.3 86.9 163.0 21.7 163.0 162.0 139.0 117.6 96.3 74.9
57 172.0 20.0 172.0 172.0 153.1 131.7 110.2 88.7 161.7 21.8 161.7 161.7 141.6 120.2 98.8 77.5
6125
77 221.1 20.7 123.0 89.2 64.3 - - - 203.9 22.4 122.7 82.9 57.5 - - -
72 204.6 20.4 153.4 128.4 103.5 78.6 - - 188.7 22.1 147.9 122.7 97.4 72.2 - -
67 188.2 20.1 183.7 167.6 142.7 117.8 92.9 - 173.4 21.8 173.4 162.6 137.3 112.1 86.9 -
62 179.4 19.9 179.4 179.1 166.0 141.1 116.2 91.3 168.7 21.6 168.7 168.3 153.8 128.6 103.4 78.2
57 178.0 20.0 178.0 178.0 168.1 143.2 118.3 93.3 167.5 21.7 167.5 167.5 156.7 131.5 106.2 81.0
7000
77 228.5 20.7 144.5 98.4 70.1 - - - 210.9 22.4 150.7 92.5 63.1 - - -
72 211.5 20.4 169.5 141.1 112.7 84.4 - - 195.1 22.0 165.0 135.9 106.8 77.7 - -
67 194.5 20.1 194.5 183.8 155.4 127.1 98.7 - 179.4 21.7 179.4 179.4 150.5 121.4 92.3 -
62 185.5 19.9 185.5 185.5 180.8 152.4 124.1 95.7 174.5 21.6 174.5 174.5 168.7 139.6 110.5 81.4
57 184.0 19.9 184.0 184.0 183.1 154.7 126.3 97.9 173.2 21.6 173.2 173.2 171.8 142.7 113.6 84.5
7875
72 212.1 20.5 176.1 147.0 117.9 88.7 - - 195.2 22.1 170.0 140.6 111.3 81.9 - -
67 195.0 20.1 195.0 189.7 162.5 133.4 104.2 - 179.4 21.7 179.4 179.4 156.8 127.4 98.0 -
62 185.9 20.0 185.9 185.9 183.6 154.5 125.4 96.2 174.6 21.6 174.6 174.6 171.7 142.3 112.9 83.5
57 184.5 20.0 184.5 184.5 184.0 154.9 125.8 96.6 173.3 21.7 173.3 173.3 172.6 143.2 113.8 84.4
8750
72 212.6 20.5 182.7 152.9 123.0 93.1 - - 195.2 22.2 175.0 145.4 115.7 86.0 - -
67 195.6 20.2 195.6 195.6 169.6 139.7 109.8 - 179.4 21.8 179.4 179.4 163.1 133.4 103.8 -
62 186.4 20.0 186.4 186.4 186.4 156.6 126.7 96.8 174.7 21.7 174.7 174.7 174.7 145.0 115.3 85.7
57 185.0 20.1 185.0 185.0 185.0 155.1 125.2 95.3 173.3 21.7 173.3 173.3 173.3 143.7 114.0 84.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF210 (17.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65