York 251934-YTG-J-0910 Air Conditioner User Manual


 
251934-YTG-J-0910
46 Johnson Controls Unitary Products
115°F 125°F
5000
77 259.6 28.3 108.9 88.3 67.7 - - - 239.1 30.7 99.0 81.5 61.1 - - -
72 242.3 27.7 146.8 126.2 105.6 85.0 - - 224.6 30.0 140.1 119.7 99.2 78.8 - -
67 225.0 27.1 184.8 164.2 143.6 122.9 102.3 - 210.0 29.3 178.3 157.8 137.4 116.9 96.5 -
62 207.6 26.7 207.6 207.2 174.1 153.5 132.9 112.3 193.3 28.9 193.3 193.3 165.0 144.6 124.1 103.7
6000
77 267.9 28.3 120.8 97.4 74.1 - - - 246.8 30.6 113.8 90.5 67.2 - - -
72 250.0 27.7 162.3 139.0 115.6 92.3 - - 231.8 29.9 155.7 132.4 109.2 85.9 - -
67 232.2 27.1 203.9 180.5 157.2 133.8 110.5 - 216.8 29.2 197.6 174.4 151.1 127.8 104.6 -
62 214.3 26.6 214.3 214.0 190.6 167.3 143.9 120.6 199.5 28.8 199.5 199.5 181.6 158.3 135.0 111.7
57 215.4 26.7 215.4 215.1 191.8 168.4 145.1 121.7 203.0 29.0 203.0 202.7 179.0 155.7 132.4 109.1
7000
77 276.2 28.2 132.7 106.6 80.5 - - - 254.5 30.5 128.5 99.4 73.4 - - -
72 257.8 27.6 177.9 151.8 125.7 99.6 - - 239.0 29.8 171.3 145.2 119.1 93.0 - -
67 239.4 27.0 223.0 196.9 170.8 144.7 118.6 - 223.5 29.1 217.0 190.9 164.8 138.7 112.7 -
62 220.9 26.6 220.9 220.8 207.2 181.1 155.0 128.9 205.7 28.7 205.7 205.7 198.1 172.0 145.9 119.8
57 222.0 26.7 222.0 221.9 208.4 182.3 156.2 130.1 209.3 28.9 209.3 209.2 195.3 169.2 143.1 117.0
8000
77 284.5 28.2 144.7 115.8 86.9 - - - 262.2 30.4 143.3 108.4 79.5 - - -
72 265.6 27.6 193.4 164.6 135.7 106.9 - - 246.3 29.7 186.8 157.9 129.0 100.1 - -
67 246.6 27.0 242.2 213.3 184.5 155.6 126.8 - 230.3 29.1 230.3 207.4 178.5 149.7 120.8 -
62 227.6 26.5 227.6 227.6 223.7 194.9 166.0 137.2 212.0 28.6 212.0 212.0 212.0 185.7 156.8 127.9
57 228.7 26.6 228.7 228.7 225.1 196.2 167.4 138.5 215.7 28.8 215.7 215.7 211.6 182.7 153.8 124.9
9000
72 264.8 27.7 204.0 172.5 141.1 109.6 - - 244.6 29.8 195.9 164.7 133.5 102.2 - -
67 245.9 27.1 243.6 223.2 191.7 160.3 128.8 - 228.7 29.1 228.7 216.0 184.7 153.5 122.2 -
62 226.9 26.6 226.9 226.9 225.0 193.5 162.0 130.5 210.5 28.7 210.5 210.5 210.5 180.6 149.3 118.1
57 228.0 26.7 228.0 228.0 226.2 194.7 163.2 131.8 214.2 28.9 214.2 214.2 212.2 180.9 149.7 118.5
10000
72 263.9 27.8 214.6 180.5 146.4 112.3 - - 242.9 29.9 205.1 171.5 137.9 104.3 - -
67 245.1 27.2 245.1 233.1 199.0 164.9 130.8 - 227.2 29.2 227.2 224.5 190.9 157.3 123.7 -
62 226.2 26.7 226.2 226.2 226.2 192.1 158.0 123.9 209.1 28.8 209.1 209.1 209.1 175.5 141.9 108.3
57 227.3 26.8 227.3 227.3 227.3 193.2 159.1 125.0 212.8 29.0 212.8 212.8 212.8 179.2 145.6 112.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF240 (20 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65