York 251934-YTG-J-0910 Air Conditioner User Manual


 
251934-YTG-J-0910
Johnson Controls Unitary Products 55
ZR180-300 Side Duct Application
ZR180 (15 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.898.
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 5 HP & Field Supplied Drive Standard 5 HP & Drive High Static 7.5 HP & Drive
4000 696 0.94 735 1.23 776 1.49 818 1.73 861 1.95 904 2.15 947 2.34 990 2.52 1031 2.68 1071 2.84 1109 3.01 1144 3.17
4400 724 1.27 763 1.56 804 1.83 846 2.07 889 2.29 932 2.49 976 2.68 1018 2.85 1060 3.02 1100 3.18 1137 3.34 1173 3.50
4800 756 1.66 795 1.95 835 2.21 878 2.45 921 2.67 964 2.87 1007 3.06 1050 3.24 1091 3.40 1131 3.56 1169 3.72 1204 3.89
5200 790 2.09 829 2.38 870 2.65 912 2.89 955 3.11 998 3.31 1041 3.49 1084 3.67 1125 3.84 1165 4.00 1203 4.16 1238 4.32
5600 826 2.57 865 2.87 906 3.13 948 3.37 991 3.59 1035 3.79 1078 3.98 1120 4.15 1162 4.32 1202 4.48 1239 4.64 1275 4.81
6000 865 3.11 904 3.40 945 3.66 987 3.90 1030 4.12 1073 4.32 1117 4.51 1159 4.69 1201 4.85 1241 5.01 1278 5.18 1314 5.34
6400 906 3.69 945 3.98 986 4.24 1028 4.48 1071 4.70 1114 4.90 1158 5.09 1200 5.27 1242 5.43 1282 5.59 1319 5.76 1355 5.92
6800 949 4.31 988 4.60 1029 4.87 1071 5.11 1114 5.33 1157 5.53 1201 5.72 1243 5.89 1285 6.06 1324 6.22 1362 6.38 1398 6.54
7200 994 4.98 1033 5.27 1074 5.54 1116 5.78 1159 6.00 1202 6.20 1245 6.39 1288 6.56 1329 6.73 1369 6.89 1407 7.05 1442 7.21
7600 1040 5.70 1079 5.99 1120 6.25 1162 6.49 1205 6.71 1249 6.91 1292 7.10 1334 7.27 1376 7.44 1416 7.60 1453 7.76 1489 7.93
7.5 HP & Field Supplied Drive
ZR240 (20 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
7.5 HP &
Field
Supplied
Drive
Standard 7.5 HP & Drive High Static 10 HP & Drive
5200 693 1.36 730 1.83 766 2.27 802 2.68 838 3.06 873 3.40 907 3.69 940 3.94 971 4.14 1002 4.28 1030 4.35 1057 4.37
5600 714 1.77 750 2.24 786 2.68 822 3.09 858 3.47 893 3.81 927 4.11 960 4.36 992 4.55 1022 4.69 1050 4.77 1077 4.78
6000 736 2.23 772 2.70 809 3.14 845 3.55 880 3.93 915 4.27 949 4.56 982 4.81 1014 5.01 1044 5.15 1073 5.23 1099 5.24
6400 760 2.73 796 3.20 832 3.64 869 4.05 904 4.43 939 4.77 973 5.06 1006 5.31 1038 5.51 1068 5.65 1096 5.72 1123 5.74
6800 785 3.28 821 3.74 858 4.18 894 4.60 930 4.97 965 5.31 999 5.61 1032 5.86 1063 6.05 1094 6.19 1122 6.27 1148 6.28
7200 812 3.87 848 4.33 885 4.78 921 5.19 957 5.57 992 5.91 1026 6.20 1059 6.45 1090 6.65 1120 6.79 1149 6.86 1175 6.88
7600 840 4.51 877 4.98 913 5.42 949 5.83 985 6.21 1020 6.55 1054 6.84 1087 7.09 1119 7.29 1149 7.43 1177 7.50 1204 7.52
8000 870 5.20 907 5.66 943 6.10 979 6.52 1015 6.89 1050 7.23 1084 7.53 1117 7.78 1148 7.98 1179 8.11 1207 8.19 1233 8.20
8400 901 5.93 938 6.40 974 6.84 1010 7.25 1046 7.63 1081 7.97 1115 8.27 1148 8.51 1179 8.71 1210 8.85 1238 8.93 1265 8.94
8800 933 6.71 970 7.18 1006 7.62 1042 8.03 1078 8.41 1113 8.75 1147 9.05 1180 9.30 1212 9.49 1242 9.63 1270 9.71 1297 9.72
9200 967 7.54 1003 8.01 1040 8.45 1076 8.86 1111 9.24 1146 9.58 1180 9.87 1213 10.12 1245 10.32 1275 10.46 1304 10.54 1330 10.55
9600 1001 8.41 1038 8.88 1074 9.32 1110 9.73 1146 10.11 1181 10.45 1215 10.74 1248 10.99 1280 11.19 1310 11.33 1338 11.41 1365 11.42
10000 1037 9.33 1073 9.79 1110 10.23 1146 10.65 1182 11.02 1217 11.36 ------------
10 HP & Field Supplied Drive