York 251934-YTG-J-0910 Air Conditioner User Manual


 
251934-YTG-J-0910
36 Johnson Controls Unitary Products
75°F 85°F
6000
72 128.6 15.7 11.3
131.8 17.1 14.7
67 116.0 15.0 42.6 14.1 119.4 16.4 38.2 9.6
62 109.6 14.3 74.3 45.8 17.3 107.1 15.8 61.4 32.9 4.4
57 101.6 14.2 101.6 54.1 25.5 100.7 15.2 66.4 37.9 9.4
7000
72 135.8 15.7 10.2
126.0 16.5 8.4
67 122.5 15.0 55.5 21.8 113.0 15.8 51.4 17.7
62 115.8 14.3 90.0 68.7 35.0 1.3 106.2 15.2 86.6 60.2 26.5
57 107.3 14.2 107.3 82.4 48.7 15.0 98.4 15.1 95.0 69.4 35.7 2.0
8000
72 143.1 15.7 9.0
132.6 16.5 2.1
67 129.1 15.0 68.4 29.5 118.9 15.8 64.6 25.7
62 122.0 14.4 91.0 91.5 52.6 13.7 111.7 15.2 90.0 87.6 48.7 9.9
57 113.0 14.3 113.0 110.7 71.8 32.9 103.5 15.1 103.5 101.0 62.1 23.2
9000
72 140.1 15.7 12.9
129.4 16.5 6.8
67 126.4 15.0 74.9 30.6 116.1 15.8 70.5 26.2
62 119.5 14.4 98.0 95.2 50.9 6.6 109.1 15.2 95.0 89.4 45.1 0.8
57 110.7 14.3 110.7 109.5 65.2 20.9 101.1 15.1 101.1 99.8 55.5 11.2
10000
72 137.1 15.7 16.7
126.3 16.5 11.5
67 123.7 15.0 86.0 31.7 113.2 15.8 76.4 26.7
62 116.9 14.4 100.0 98.9 49.2 106.4 15.2 84.0 80.0 41.5
57 108.3 14.3 108.3 108.3 58.6 35.0 98.6 15.1 98.6 98.6 48.9 15.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR240 (20 Ton) Alternate Reheat Mode (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
85 80 75 70 65 85 80 75 70 65
No Sensible Cooling Capacity