Vista -10SE Home Security System User Manual


 
VISTA-10SE Installation and Setup Guide
A-2
UL NOTICES
1. This is a "Grade A" residential system.
2. The 4285/4286 VIP Module and 7720PLUS or 7820 Long-Range Radios have not been UL
tested and cannot, therefore, be used in a UL installation.
3. The Entry Delay (field
38) cannot be greater than 45 seconds for UL installations.
4. The maximum number of reports per armed period (field
92) must be unlimited (set to 1)
for UL installations.
5. Periodic testing (field
49) must be at least every 24 hours (set to 1) for UL installations.
6. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations.
7. Downloading is not permissible for UL installations unless an installer is present at the
installation site.
CALIFORNIA STATE FIRE MARSHAL (CSFM) AND UL RESIDENTIAL FIRE
24 HOUR BATTERY BACKUP REQUIREMENTS
The California State Fire Marshal and UL have regulations that require all residential fire alarm control
panels to be provided with a backup battery that has sufficient capacity to operate the panel and its
attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes
in the intended fire alarm signaling condition.
This control panel can meet these requirements without using a supplementary power supply, provided
that the panel's auxiliary power and bell output currents are limited as indicated below.
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS AND UL LISTED
RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
OUTPUT CURRENT
TOTAL
MAXIMUM
AUXILIARY CURRENT
BATTERY CAPACITY
TO USE (Amp/Hrs)
RECOMMENDED
BATTERY
(Yuasa Model No.)
600mA maximum total
of
auxiliary power
plus bell output
currents
45mA
160mA
200mA
425mA
500mA
4AH
7AH
8AH
14AH
17.2AH
NP4-12
NP7-12
NP4-12 (two)
NP7-12 (two)
NPG18-12
NOTE:
Use two batteries, connected in parallel. Obtain an ADEMCO Battery Harness kit. A dual-battery
harness is provided with the kit. Both batteries will fit inside the panel's cabinet.