4-2
3.
To meet NFPA 72 requirements, you must use a supervisory module to supervise power
(e.g., System Sensor No. A77-716B Relay module).
+
+
1000
OHMS
EOLR
HEAT
DETECTOR
HEAT
DETECTOR
ZONE 5
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B
VIOLET
4-WIRE SMOKE
OR COMBUSTION
DETECTORS
TO HI SIDE OF
TO LO SIDE
AUX PWR
OUTPUT
TERMINALS
5
4
+
+
BLK
+
V10SE-010-V0
Figure 7. 4-wire Smoke Detector Connections (Zone 5)
Compatible System Sensor 4-Wire Smoke/Combustion Detectors
1412
4-wire ionization products of combustion detector
2412
4-wire photoelectric smoke detector
2412TH
4-wire photoelectric smoke detector w/135°F (57°C) heat detector
A77716B
EOL relay module (supervisory module for wired 4-wire fire zone)
2112/24T
Low-profile 4-wire photoelectric smoke detector w/135°F (57°C) heat
detector
Programming Hardwired Zones
Each zone must be programmed into the system using the
56 Zone Programming Mode or
58 Expert Programming Mode, which assigns characteristics that define the way the system
responds to faults on that zone. Refer to the ZONE RESPONSE TYPE DEFINITIONS and
ZONE PROGRAMMING sections for specific instructions on programming hardwired zones.