Viking VCWB300 Carpet Cleaner User Manual


 
and appropriate zone valve based upon the temperature at the evaporator thermistor and
will turn off the zone valve based upon the temperature at the chamber thermistor.
Temperature readout and setting: Pressing the zone button will change which chamber
is selected for adjustments. The selected chamber will have a bar displayed over the
temperature reading on the VFD. Pressing the higher or lower buttons will raise or lower
the set point of the selected chamber in one degree F increments. Every time any set
point is changed a “set time” delay will start. When the “set time” delay is completed
without another change in the temperature the currently displayed number will become
the new set point. The new set point will be stored in non-volatile memory. The unit will
begin controlling the particular chamber to the new set point, and the actual chamber
temperature will be displayed. Temperature can be displayed in either Degrees F
(default) or in Degrees C. It can be changed from one to the other by pressing and
holding both the display on/off and the display alarm buttons simultaneously for 5
seconds. The display will show “F” or “C” appropriately. This setting will be stored in
non-volatile memory and will be saved during period of power loss.
Display off: To turn the display off, momentarily press the display. The display will turn
off as soon as the button is released.
To turn the display on, momentarily press the display button. The display will turn on as
soon as the button is released.
Compressor protection: At any time the compressor needs to start, including that power
up the appropriate zone valve will energize for 60 seconds before the compressor is
allowed to start. This is intended to allow to discharge any pressures in the system so that
the compressor will not start under heavy load. Any time that all chambers reach set
temperatures(s), the compressor will continue to run for an additional 30 seconds. This is
intended to reduce compressor start / stop cycles as the various chambers call for cooling.
Fan operation: The evaporator fans, if running will shut off whenever the door switch
opens and turns back on when the door switch closes. When operating in Holiday Mode
the Fan(s) will not turn off, if running, when the door switch opens.
Chamber lighting: The light inside the chambers can be always on, or only on when the
door switch is open. Pressing the lights button on the front panel toggles this setting.
Also see holiday mode.
Alarm security: Alarm operation can be toggled on or off by pressing the alarm front
panel button for 2 seconds. When the temperature inside any chamber is higher than the
set temperature by more than 5 degrees F for longer than the “2 hours” delay, the display
will flash on and off and an audible signal will sound. When the alarm mode is active, an
enunciator will appear in the display. Upon initial power-up, the alarm will be disabled
for a start-up delay to allow for the unit to reach temperature. The alarm can be disabled
by pressing the alarm off button. A door alarm is provided that will sound if the door
switch is open for longer than the door alarm delay. The alarm will shut off upon re-
closing the door and the delay time will be reset. Temperature alarm operation will be
inhibited in show room mode. Home security contacts will transfer during an alarm
condition. When operating in Holiday Mode, the high temperature alarm and door
alarms are disabled.
7