Trane PKG-PRC002-EN Air Conditioner User Manual


 
Electrical Data
PKG-PRC002-EN80
SCWF/SCRF
Table ED-6. Single Stage Electric Heat Electrical Data
SXWF SXRF Heat 200V 460V
Size Size Kw Amps Amps
20 - 18 50 21.7
22 - 18 50 21.7
25 20 18 50 21.7
29 25 23 63.8 27.7
32 29 23 63.8 27.7
35 30 27 75 32.5
38 35 27 75 32.5
42 - 31.5 87.4 37.9
46 40 31.5 87.4 37.9
52 - 39 108.3 46.9
58 50 39 108.3 46.9
65 - 48 133.2 57.7
72 - 48 133.2 57.7
80 60 48 133.2 57.7
Note:
Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.
Table ED-7. CCRC/CIRC Condenser Electrical Data
Unit Size Rated MFS.
Tons Voltage # Fans FLA (ea.) LRA (ea.) MCA MCB
20, 29 200 4 4.1 20.7 17.43 20
460 4 1.8 9 7.65 15
575 4 1.4 7.2 5.95 15
35, 40 200 6 4.1 20.7 25.63 30
460 6 1.8 9 11.25 15
575 6 1.4 7.2 8.75 15
50, 60 200 8 4.1 20.7 33.83 40
460 8 1.8 9 14.85 20
575 8 1.4 7.2 11.55 15
Note:
All motors for CCRC/CIRC units are rated at 1 hp (.7457 kW).