General Data
PKG-PRC002-EN 19
SCRF/SIRF
20-60 Tons
Table GD-4. SCRF/SIRF Air-Cooled Self-Contained
Unit Size 20 25 29 30 35 40 50 60
Compressor Data
Quantity 2 1/1 1/1 3 3 2/1 3 4
NominalTon/Comp 10 15/10 15/10 10 10 10/15 15 15
Circuits 2 2 2 2 2 2 2 2
Evaporator Coil Data
Rows 3 2 4 3 4 4 4 6
Sq. Ft. 21.81 29.98 29.98 31.35 31.35 38.57 49.09 49.09
Sq. m (2.03) (2.79) (2.79) (2.91) (2.91) (3.58) (4.56) (4.56)
FPF 144 144 144 120 144 144 144 144
Evaporator Fan Data
Quantity 1 1 1 1 1 1 1 1
Size (Dia. - inches) 16.5" 18.25" 18.25" 20" 20" 25" 25" 27.5"
Size (Dia. - mm) (419.1) (463.6) (463.6) (508) (508) (635) (635) (698.5)
Minimum HP 5 5 5 5 5 7.5 10 10
Minimum kW (3.73) (3.73) (3.73) (3.73) (3.73) (5.59) (7.46) (7.46)
Maximum HP 20 25 25 25 25 40 40 50
Maximum kW (14.91) (18.64) (18.64) (18.64) (18.64) (22.37) (37.29) (37.29)
Minimum Design CFM 6500 8700 8700 9100 9880 11960 15080 20800
Minimum Design liters / sec. (3068) (4106) (4106) (4295) (4663) (5645) (7117) (9817)
Maximum Design CFM 10625 12325 13600 14875 16150 19550 24650 29800
Maximum Design liters / sec. (5014) (5817) (6418) (7020) (7622) (9227) (11634) (14064)
General Data
EER 10.8 10.8 10.8 11.0 11.2 11.3 10.8 9.9
IPLV 11.8 12.1 11.4 12.8 12.6 12.5 12.0 10.0
Refrigerant Charge - lbs. R-22 57.2 66.7 72 57 57.2 66.7 72 72
Refrigerant Charge - kg R-22 (25.9) (30.3) (32.7) (25.9) (25.9) (30.3) (32.7) (32.7)
Capacity Steps - % 100/53/0 100/62/39/0 100/59/39/0 100/65/31/0 100/65/30/0 100/70/41/30/0 100/65/30/0 100/73/46/20/0
Filter Data
Quantity 8 8 8 8 8 4 4 4
Size (inches) 20x18x2 20x18x2 20x18x2 20x18x2 20x18x2 16x20x2 16x20x2 16x20x2
Size (mm) (508x457x51) (508x457x51) (508x457x51) (508x457x51) (508x457x51) (406x508x51) (406x508x51) (406x508x51)
Quantity 4 4 4 4 4 8 8 8
Size (inches) 20x20x2 20x20x2 20x20x2 20x20x2 20x20x2 16x25x2 16x25x2 16x25x2
Size (mm) (508x508x51) (508x508x51) (508x508x51) (508x508x51) (508x508x51) (406x635x51) (406x635x51) (406x635x51)
Quantity 222
Size (inches) 20x20x2 20x20x2 20x20x2
Size (mm) (508x508x51) (508x508x51) (508x508x51)
Quantity 444
Size 20x25x2 20x25x2 20x25x2
Size (mm) (508x635x51) (508x635x51) (508x635x51)
CCRC/CIRC Unit Match 20 29 29 35 35 40 50 60
Notes:
1. Compressors are Trane 3D
®
scroll.
2.EER and IPLV are rated in accordance to the ARI Standard 340/360-93. Based on 80/67 F (26.7/19.4 C) to the evaporator coil, nominal airflow and 95 F (35 C) ambient.
3.All units operate with R-22. Units ships with a dry nitrogen holding charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Filter sizes are for units without hot water or steam heating coils
Table GD-5. SCRF/SIRF Refrigerant Circuits,
Number of Compressors by Circuit
Circuit 1 2
Unit Size
20 Ton 1-10T 1- 10T
25/29 Ton 1-15T 1-10T
30/35 Ton 2-10T 1-10T
40 To n 1- 10T, 1-1 5T 1-15T
50 To n 2-15T 1-15T
60 To n 2-15T 2-15T
Note: This table depicts compressor location in unit, plan
view from left corner