Trane Modu Heating System User Manual


 
SCXG-SVX01B-EN 81
Figure O-GI-2. Velocity Pressure Trans-
ducer/Solenoid Assembly.
VO relay energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
PURGE sequence D
This sequence could be used for purging
the air out of a building before coming out
of unoccupied mode of operation on VAV
units. Also, it can be used to purge smoke
or stale air.
Supply fan on
Supply fan VFD on (60 Hz)
(if equipped)
Inlet guide vanes/VAV boxes Open
(if equipped)
Outside air damper Open
Heat all stages Off, Modulating heat
output at 0 vdc
Occupied/unoccupied output Energized
VO relay Energized
Exhaust fan (field-installed) - On
Exhaust damper (field-installed) - Open
PURGE with duct pressure control E
This sequence can be used when supply
air control is required for smoke control.
Supply fan on
Supply fan VFD on (if equipped)
Inlet guide vanes controlled by supply
air pressure control function with
supply air pressure high limit disabled
Outside air dampers open
Heat all stages off, hydronic heat
output at 0 vdc
Occupied/unoccupied output energized
VO relay energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
Note: Each system (cooling, exhaust,
supply air, etc.) within the unit can be
redefined in the field for each of the five
sequences, if required. Also the definitions
of any or all of the five sequences may be
locked into the software by simple key
strokes at the human interface panel. Once
locked into the software, the sequences
cannot be changed.
Trane Communications
Interface Module (TCI) - Option
used with Trane ICS
TM
The Trane communication interface
module allows external setpoints for
most of the unit functions to be
communicated to the unit's UCM network
via a Trane ICS
TM
systems. DIP switch
settings on the TCI module for this
Owner
General
Information
application are; switch 1 off, 2 on, and
3 off.
Exhaust/Comparative
Enthalpy Module (ECEM) - On
Units with Comparative
Enthalpy Option
The exhaust/comparative enthalpy
module receives information from the
return air humidity sensor, and the RTM
outside air temperature sensor and
outside air humidity sensor, the outside
air humidity sensor and temperature
sensor to utilize the lowest possible
enthalpy level when considering
economizer operation. In addition, it
receives space pressure information to
maintain the space pressure within the
setpoint control band. Refer to the Figure
O-GI-1 for humidity vs. voltage values.
Ventilation Control Module
(VCM) - Available only with
Tra q Damper Option
The ventilation control module (VCM) is
located in the airside economizer section
of the unit and linked to the units UCM
network. Using a velocity pressure
transducer/solenoid (pressure sensing
ring) in the fresh air section allows the
VCM to monitor and control fresh air
entering the unit to a minimum airflow
setpoint. See Figure O-GI-2 for a detail
view of the velocity pressure transducer/
solenoid assembly.
An optional temperature sensor can be
connected to the VCM to enable control
of a field installed fresh air preheater.
Also, a field-provided CO
2
sensor can be
connected to the VCM to control CO
2
reset. The reset function adjusts the
minimum cfm upward as the CO
2
concentrations increase. The maximum
effective (reset) setpoint value for fresh
air entering the unit is limited to the
systems operating cfm. Table O-GI-5 lists
the minimum outside air cfm vs. input
voltage.
Table O-GI-5. Minimum Outside Air
Setpoint w/VCM Module and Traq
Sensing.
Unit Input Volts CFM
SXWG 20 0.5 - 4.5 vdc 6,350-8,500
SXWG 25 0.5 - 4.5 vdc 7,250-10,625
SXWG 30 0.5 - 4.5 vdc 7,250-12,750
SXWG 35 0.5 - 4.5 vdc 7,250-14,875
SXRG 20 0.5 - 4.5 vdc 7,250-8,500
SXRG 25 0.5 - 4.5 vdc 7,250-10,625
SXRG 32 0.5 - 4.5 vdc 7,250-13,600
Figure O-GI-1. ECEM Relative Humidity vs.
Voltage.