Trane GEH Heat Pump User Manual


 
72 WSHP-SVX01D-EN
Electrical
Requirements
E7-Electrical performance (continued)
E8-Electrical minimum and maximum
Model No. Volts Total
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Compres.
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
Num
Minimum
Circuit
Ampacity
Maximum
Overcur-
rent
Protec-
tive
Device
Electric
Heat
kW
Electric
Heat
Amps
GEV 180 208/60/3 59.4 25.00 164.0 2 35.0 9.40 3 1 65.7 90
230/60/3 58.2 25.00 164.0 2 35.0 8.20 3 1 64.5 80
380-420/50/3 27.4 12.00 90.5 2 17.0 3.40 2 1 30.4 40
460/60/3 28.1 12.00 100.0 2 17.0 4.10 3 1 31.1 40
575/60/3 21.9 9.30 78.0 2 13.0 3.30 3 1 24.2 30
208/60/3 66 25.00 164.0 2 35.0 16.00 5 1 72.3 90
230/60/3 64 25.00 164.0 2 35.0 14.00 5 1 70.3 90
380-420/50/3 29.5 12.00 90.5 2 17.0 5.50 3 1 32.5 40
460/60/3 31 12.00 100.0 2 17.0 7.00 5 1 34.0 45
575/60/3 23.8 9.30 78.0 2 13.0 5.20 5 1 26.1 35
208/60/3 75 25.00 164.0 2 35.0 25.00 7.5 1 81.3 100
230/60/3 71.6 25.00 164.0 2 35.0 21.60 7.5 1 77.9 100
380-420/50/3 33.3 12.00 90.5 2 17.0 9.30 5 1 36.3 45
460/60/3 34.8 12.00 100.0 2 17.0 10.80 7.5 1 37.8 45
575/60/3 26.8 9.30 78.0 2 13.0 8.20 7.5 1 29.1 35
GEV 240 208/60/3 79.4 31.70 232.0 2 49.5 16.00 5 1 87.4 110
230/60/3 77.4 31.70 261.0 2 49.5 14.00 5 1 85.4 110
380-420/50/3 38.9 16.70 133.0 2 26.0 5.50 3 1 43.1 50
460/60/3 35.2 14.10 112.0 2 22.0 7.00 5 1 38.7 50
575/60/3 27.6 11.20 92.0 2 17.5 5.20 5 1 30.4 40
208/60/3 88.4 31.70 232.0 2 49.5 25.00 7.5 1 96.4 125
230/60/3 85 31.70 261.0 2 49.5 21.60 7.5 1 93.0 110
380-420/50/3 42.7 16.70 133.0 2 26.0 9.30 5 1 46.9 60
460/60/3 39 14.10 112.0 2 22.0 10.80 7.5 1 42.5 50
575/60/3 30.6 11.20 92.0 2 17.5 8.20 7.5 1 33.4 40
208/60/3 96.4 31.70 232.0 2 49.5 33.00 10 1 104.7 125
230/60/3 91.4 31.70 261.0 2 49.5 28.00 10 1 99.4 125
380-420/50/3 46.4 16.70 133.0 2 26.0 13.00 7.5 1 50.6 60
460/60/3 42.2 14.10 112.0 2 22.0 14.00 10 1 45.7 50
575/60/3 33.4 11.20 92.0 2 17.5 11.00 10 1 36.2 45
208/60/3 108.2 31.70 232.0 2 49.5 44.80 15 1 119.5 150
230/60/3 104 31.70 261.0 2 49.5 40.60 15 1 114.2 150
380-420/50/3 50.9 16.70 133.0 2 26.0 17.50 10 1 55.3 70
460/60/3 48.5 14.10 112.0 2 22.0 20.30 15 1 53.6 70
575/60/3 38.6 11.20 92.0 2 17.5 16.20 15 1 42.7 50
GEV 300 208/60/3 110.2 47.10 245.0 2 66.0 16.00 5 1 122.0 150
230/60/3 108.2 47.10 245.0 2 66.0 14.00 5 1 120.0 150
380-420/50/3 44.7 19.60 118.0 2 27.5 5.50 3 1 49.6 60
460/60/3 46.2 19.60 125.0 2 27.5 7.00 5 1 51.1 70
575/60/3 36.8 15.80 100.0 2 22.2 5.20 5 1 40.8 50
208/60/3 119.2 47.10 245.0 2 66.0 25.00 7.5 1 131.0 175
230/60/3 115.8 47.10 245.0 2 66.0 21.60 7.5 1 127.6 150
380-420/50/3 48.5 19.60 118.0 2 27.5 9.30 5 1 53.4 70
460/60/3 50 19.60 125.0 2 27.5 10.80 7.5 1 54.9 70
575/60/3 39.8 15.80 100.0 2 22.2 8.20 7.5 1 43.8 50
208/60/3 127.2 47.10 245.0 2 66.0 33.00 10 1 139.0 175
230/60/3 122.2 47.10 245.0 2 66.0 28.00 10 1 134.0 175
380-420/50/3 52.2 19.60 118.0 2 27.5 13.00 7.5 1 57.1 70
460/60/3 53.2 19.60 125.0 2 27.5 14.00 10 1 58.1 70
575/60/3 42.6 15.80 100.0 2 22.2 11.00 10 1 46.6 60
208/60/3 139 47.10 245.0 2 66.0 44.80 15 1 150.8 175
230/60/3 134.8 47.10 245.0 2 66.0 40.60 15 1 146.6 175
380-420/50/3 56.7 19.60 118.0 2 27.5 17.50 10 1 61.6 80
460/60/3 59.5 19.60 125.0 2 27.5 20.30 15 1 64.6 80
575/60/3 47.8 15.80 100.0 2 22.2 16.20 15 1 51.9 60
Digit 8 Rated
Voltage
HZ Ph Minimum
Utilization
Voltage
Maximum
Utilization
Voltage
0 115 60 1 104 126
1
208 60 1 197 229
2
230 60 1 207 253
3
208 60 3 187 229
4
460 60 3 414 506
E8-Electrical minimum and maximum (continued)
Digit 8 Rated
Voltage
HZ Ph Minimum
Utilization
Voltage
Maximum
Utilization
Voltage
5
575 60 3 518 633
6
220-240 50 1 198 264
7
265 60 1 239 292
8
230 60 3 207 253
9
380-415 60 3 342 456