The following steps were sequenced
to aid in the installation and mating of
a water side economizer to a water-
source heat pump (GEH 1/2 to 5 ton).
1 Remove the control side service
panel of the water-source heat
pump unit.
2 Remove rubber isolation grom-
mets from the return-air section.
Place them in a convenient loca-
tion.
3 Attach ducted panel to the water-
source heat pump unit with six
factory provided Torx
®
head
screws. This panel is shipped
loose with the water-source heat
pump but must be field installed
to the unit.
Step 3
4 Attach the water side economiz-
ing unit to the ducted panel of the
water-source heat pump with 10-
factory provided Torx head
screws. The economizing pack-
age fits to the outside of the of the
water-source heat pump. Trane
recommends the mating of the
systems be made via 3-screws
spaced evenly across the top,
3-screws spaced evenly across
the bottom (installed immediate-
ly after hanging the unit), and 2-
screws on each side.
Step 4
5 Install the 18-inch steel braided
hose between the upper most
piping connection of the econo-
mizer, and the water-in of the
heat pump. The hose is shipped
loose with the water-side econo-
mizer.
Step 5
6 Install the SUPPLY and RETURN
hoses to the (1) 2-position valve’s
threaded connection (2) water-
out threaded connection of the
water-source heat pump.
Step 6
7 VERIFY
The control board for the water
side economizer is located at the
back of the control box. The tem-
perature rating of this board is
factory set to 55ºF.
For units with boilerless (electric
heat) control and water side
economizer, the boilerless con-
trol board is factory set to 45ºF.
Step 7
Installation
Waterside Economizer