Trane BAS-SVP10A-EN Thermostat User Manual


 
42 BAS-SVP10A-EN
Trane Communicating Thermostat Points List
The following tables provide side by side lists of Tracer SC pointsand Communicating Thermostat
device point names and related information.
TStat_Fan_Coil_Trane
Table 44. Points Available in the TStat_Fan_Coil_Trane Template
Tracer SC Point Name
TStat Device Point
Name
Point
Type
Point
Instance
Data
Normaliza-
tion
Diagnostic Present Service Alarm BI 37
Dirty Filter Alarm Filter Alarm BI 36
Discharge Air Temperature Supply Temperature AI 12
Display Temperature Scale Temperature Scale BV 51
Emergency Heat Status AUX Status BI 25
Fan Mode BAS Fan Mode MV 17 Yes
Heat Cool Mode Request System Mode MV 16 Yes
Keypad Lockout Keypad Lockout MV 19
Minimum Heating Cooling Setpoint
Differential
Deadband AV 63
Occupancy Input Local Motion BI 32
Occupancy Request Occupancy Command MV 18 Yes
Occupancy Status Effective Occupancy MV 33 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 40
Occupied Heating Setpoint Occupied Heat Setpoint AV 39
Occupied Standby Cooling Setpoint Stand-by Cool Setpoint AV 42
Occupied Standby Heating Setpoint Stand-by Heat Setpoint AV 41
Outdoor Air Temperature Outdoor Temperature AV 9
Space Temperature Active Room Temperature AV 7
Supply Fan Staged Speed Status Fan Status MV 28 Yes
Timed Override Duration Setpoint Temporary Occupancy Time MV 62
Unoccupied Cooling Setpoint Unoccupied Heat Setpoint AV 43
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 44
PI Heating Demand AV 21
PI Cooling Demand AV 22
Password Value AV 56
Heating Setpoint Limit AV 58
Cooling Setpoint Limit AV 59
Stand-by Time AV 67
Unoccupied Time AV 68
BI 1 Status BI 29
BI 2 Status BI 30
UI 3 Status BI 31
Window Alarm BI 35
Room Temp Override BV 8
AUX Command BV 14
Menu Scroll BV 49
Auto Mode Enable BV 50
Setpoint Type BV 60
Setpoint Function BV 61
Reheat Time Base BV 64
Auto Fan BV 66
Control Type BV 75
Sequence of Operation MV 15
Heating Valve Status MV 26