12 BAS-SVP10A-EN
Summary of BACnet Objects
Standard Object Types Supported
Footnotes for fan coils:
a : Present_Value and Out_of_Service properties are writable for every AV objects except PI Heating Demand (AV21) and
PI Cooling Demand (AV22).
b : Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if Room Temp Override
(BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
AV 96 Present_Value (R) √
Humidification High Limit
Spt (Setpoint)
AV 97 Present_Value (R,W) √
Low RH Setpoint AV 98 Present_Value (R,W) √
Low Temp Reset RH
Setpoint
AV 99 Present_Value (R,W) √
High Temp Reset RH
Setpoint
AV 100 Present_Value (R,W) √
Humidifier Output AV 101 Present_Value (R) √
Table 3. Rooftop and heat pump ungrouped objects
Object Name
Type and
Instance Object Property
Rooftop
-1010
Heat Pump
-2010
Dehumidifi-
cation
-1050
Table 4. Standard object types supported
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported Writable Properties
Analog Input Reliability Out_of_Service
Analog Value Reliability Present_Value (a,b,e)
Out_of_Service (a,e)
Object_Name (c ,f)
Binary Input Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group N/A N/A
Multi-state Value Reliability
States_Text
Present_Value (d)
Out_of_Service (d)
Schedule
(Rooftop and heat
pump only)
Weekly_schedule Present_Value
Weekly_Schedule