Trane BAS-SVP10A-EN Thermostat User Manual


 
18 BAS-SVP10A-EN
BACnet Object Properties
Temporary Occupancy
Time
MV 62
1 0 hour
2 hours
2 1 hour
3 2 hours
4 3 hours
5 4 hours
6 5 hours
7 6 hours
8 7 hours
9 8 hours
10 9 hours
11 10 hours
12 11 hours
13 12 hours
14 13 hours
15 14 hours
16 15 hours
17 16 hours
18 17 hours
19 18 hours
20 19 hours
21 20 hours
22 21 hours
23 22 hours
24 23 hours
25 24 hours
Proportional Band MV 65
1 3 3 F 1.2 C
3
2 4 4 F 1.7 C
3 5 5 F 2.2 C
4 6 6 F 2.8 C
5 7 7 F 3.3 C
6 8 8 F 3.9 C
7 9 9 F 5.0 C
8 10 10 F 5.6 C
Floating Motor
Timing
MV 76
1 0.5 minute
1.5 minutes
2 1 minute
3 1.5 minutes
4 2 minutes
5 2.5 minutes
6 3 minutes
7 3.5 minutes
8 4 minutes
9 4.5 minutes
10 5 minutes
11 5.5 minutes
12 6 minutes
13 6.5 minutes
14 7 minutes
15 7.5 minutes
16 8 minutes
17 8.5 minutes
18 9 minutes
Table 13. Additional MV Values (continued)
Object Name Object ID BACnet Index Text Default Value