Trane BAS-SVP10A-EN Thermostat User Manual


 
14 BAS-SVP10A-EN
BACnet Object Properties
This section lists ranges, enumerations, and values for the set of Communicating Thermostat
objects.
Fan Coil Object Properties
Table 6. List of property value range restrictions
Object Name
Object Type and
Instance
Minimum Range
Value
Maximum Range
Value Default Value
Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (50°C) N/A
Outdoor Temperature AV 9 -39°F (-40°C) 121.9°F (50°C) N/A
Room Humidity AV 10 5% 90% N/A
Supply Temperature AI 12 -39.9°F (-40°C) 121.9°F (50°C) N/A
PI Heating demand AV 21 0% 100% 0%
PI Cooling demand AV 22 0% 100% 0%
Occupied Heat
Setpoint
AV 39 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool
Setpoint
AV 40 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Stand-by Heat
Setpoint
AV 41 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Stand-by Cool
Setpoint
AV 42 54°F (12°C) 100°F (37.5°C) 74°F (24°C)
Unoccupied Heat
Setpoint
AV 43 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Unoccupied Cool
Setpoint
AV 44 54°F (12°C) 100°F (37.5°C) 80°F (26.5°C)
Password Value AV 56 0 1000 0
Heating Setpoint Limit AV 58 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 59 54°F (12°C) 100°F (37.5°C) 54°F (12°C)
Deadband AV 63 2°F (1°C) 5°F (2.5°C) 2°F (1°C)
Stand-by Time AV 67 0.5 Hours 24.0 Hours 0.5 Hours
Unoccupied Time AV 68 0.0 Hours 24.0 Hours 0.0 Hours
RH Setpoint AV 45 30% 100% 50%
Dehumidification
Hysterisys
AV 46 2% 20% 5%
Dehumidification MAX
cooling
AV 47 20% 100% 100%
Table 7. List of property enumeration sets for BV objects and BI objects
Object Name
Object Type and
instance Inactive_Text Active_Text Default value
Room Temp Override BV 8 Normal Override Normal
Room Humidity
Override
BV 11 Normal Override Normal
Dehumidification
Lockout
BV 13 Disabled Enabled Enabled
AUX Command BV 14 Off On Off
Dehumidification
Status
BI 23 Off On Off
Aux Status BI 25 Off On Off
BI 1 Status BI 29 Deactivated Activated Deactivated
BI 2 Status BI 30 Deactivated Activated Deactivated
UI 3 Status(*) BI 31 Deactivated Activated Deactivated
Local Motion BI 32 No Motion Motion No Motion
Window Alarm BI 35 Off On Off