Trane BAS-SVP10A-EN Thermostat User Manual


 
40 BAS-SVP10A-EN
Data Normalization
Template: TStat_RTU_Trane
This section lists special data normalizations for points in this template.
Tracer SC Point name: Occupancy Status
BACnet point name, type, and instance: Effective Occupancy (MV 34)
Table 36. Tracer SC writing to the heat pump (Heat Cool Mode Request)
Tracer SC state and text Heat pump state and text
1 - Auto 2 - Auto
2 - Heat 4 - Heat
3 - Morning Warm-up 4 - Heat
4 - Cool 3 - Cool
5 - Night Purge 3 - Cool
6 - Pre Cool 3 - Cool
7 - Off 1 - Off
8 - Test 2 - Auto
9 - Emergency Heat 5 - Emergency
10 - Fan Only 2 - Auto
11 - Free Cool 3 - Cool
12 - Ice-Making 3 - Cool
13 - Max Heat 4 - Heat
14 - Economizer 3 - Cool
15 - Dehumidify 3 - Cool
16 - Calibrate 2 - Auto
Table 37. Reading from Heat Pump to Tracer SC (Heat Cool Mode Request)
Heat pump state and text Tracer SC state and text
1 - Off 7 - Off
2 - Auto 1 - Auto
3 - Cool 4 - Cool
4 - Heat 2 - Heat
5 - Emergency 9 - Emergency Heat
Table 38. Tracer SC writing to the rooftop unit (Occupancy Status)
Tracer SC state and text Rooftop unit state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Occupied Bypass 1 - Occupied
4 - Occupied Standby 1 - Occupied
5 - Auto 1 - Occupied
Table 39. Reading from rooftop unit to Tracer SC (Occupancy Status)
Rooftop unit state and text Tracer SC state and text
1 - Occupied 1 - Occupied
2 - Unoccupied 2 - Unoccupied
3 - Temporary Occupied 1 - Occupied